background image

AT-G-DETECT

 

Gas Sensing System

LEAK DETECTION SOLUTIONS

8

M. DOUBLE CHECK CONNECTIONS ARE CORRECT

To make sure the gas detectors are wired up correctly you can check the voltages at the sensor 
cable terminal blocks on the controller PCB or sensor PCB using a 0-10V voltmeter as outlined 
below in Table 1.

Place the negative probe on terminal position 4 and with the positive on1, 3, 2, check the Volts 
values. The readings are lower at the sensor due to power drop in the line.

The terminals should have the under listed values:

Position 
Number

At the sensor

Controller

Without sensor 

fi

 tted

4

Is the negative side of the power supply

Negative

Negative

1

Power Supply 7.2V minimum, unless you 
have power drop reduction

+10V

+12 – 15V

3

Approximately 4-5V

+4.8 – 5V

+5V

2

One level system – sensor standby 
voltage* as shown on the calibration 
label on the side of the enclosure.
Two level system – typical internal 
reference values, approximately

(0=Fault) 
+0.4V
+1.6V
+2.8V

0
Sensor in standby 
Low Alarm Condition 
High Alarm Condition

* The voltage signal from the sensor will on power up start high and gradually fall (in clean air)
to the SSV value shown on the calibration label.

You can monitor this as follows:

1 level systems: Connect a Voltmeter and monitor voltage between Pins 4 (-Ve) & 2 (+Ve) of the 
sensor terminal connector block for each channel in turn (CN1,CN2 Etc.)

2 level systems: Connect voltmeter and monitor voltage between TP5 (0V) & TP4 (+Ve).

Important: 

All information, including illustrations, is believed to be reliable. Users, however, 

should independently evaluate the suitability of each product for their application. Aquilar 
Limited makes no warranty as to the accuracy or completeness of the information, and 
disclaims any liability regarding its use. The only obligations of Aquilar Limited are those in 
the Aquilar Standard Terms and Conditions of Sale for this product, and in no case will Aquilar 
Limited be liable for any incidental, indirect, or consequential damages arising from the sale, 
resale, use or misuse of the product. Speci

fi

 cations are subject to change without notice. In 

addition, Aquilar Limited reserves the right to make changes – without noti

fi

 cation to Buyer

– to processing or materials that do not a

 ect compliance with any applicable speci

fi

 cation.

AquiTron

 is a trademark of 

AquiTron Limited

Aquilar

 is a trademark of 

Aquilar Limited

V

2

 

04

.201

9

Unit 30, Lawson Hunt Industrial Park, 

Broadbridge Heath, Horsham, West Sussex, 

RH12 3JR
+44 (0) 1403 216100
[email protected]
www.aquilar.co.uk

Содержание AquiTron AT-G-DETECT

Страница 1: ...AT G DETECT Refrigerant Gas Sensing System Check Calibration Procedure AquiTron CA L I B R AT I O N P R O C E D U R E...

Страница 2: ...ective is to establish if the sensor is reacting to the gas and all the sensor outputs are working correctly A quantified bump test is one where gas of a know concentration is used CALIBRATION This co...

Страница 3: ...r does not go into alarm carry out a gas calibration If the factory set point information is not on the calibration label as with older units check the serial number of your gas detector on the rating...

Страница 4: ...OULES 1 Make sure that both the ampoules and the calibration beaker are clean and dry 2 Unscrew the beaker hold screw and place the ampoule so that it sits in the base of the beaker 3 Tighten on the s...

Страница 5: ...o the controller to monitor sensor response Expose the sensor to gas from the cylinder You can place the entire sensor into a plastic bag or use a plastic hose hood to direct gas to the sensor head G...

Страница 6: ...3 minute alarm delay on a one level system by moving the jumper link at JP1 to the o position Two adjustments are required and they are all performed on the controller unit A Sensor Standby Voltage S...

Страница 7: ...used drift B Alarm Threshold Voltage ATV Low Treshhold Connect voltmeter between TP5 0V TP2 Ve set the voltage asshown on the calibration label by adjusting pot P8 High Threshold Connect voltmeter bet...

Страница 8: ...r extreme humidity or temperature conditions you may adjust the settings to compensate One Level Systems You should reduce the SSV level in 0 5V increments until the condition clears Two Level Systems...

Страница 9: ...libration label You can monitor this as follows 1 level systems Connect a Voltmeter and monitor voltage between Pins 4 Ve 2 Ve of the sensor terminal connector block for each channel in turn CN1 CN2 E...

Отзывы: