Statox 560 Getting started 

 

 

Issue 12/2016 

 

Page 1 of 10 

 

 

 

Getting started with the Statox 560 

 

 

 

1

 

Safety Advice 

 

Read and observe this manual carefully. Store it in a safe place. 

 

The Statox 560 must not be operated other than in the specified ambient conditions (see 
Technical Data, page 10). 

 

In particular the regulations with regards to the protection regulations for instance DIN EN 60079-
14 must be observed. 

 

Installation must be performed by trained and authorized personnel. Only original Compur 
Monitors parts may be used. 

 

The Statox 560 must not be connected to mains! The supply voltage is 24 (16-30) VDC. 

 

All outputs of the Statox 560 may only be operated with 30 VDC. 

 

Damaged or modified sensor heads must not be used. 

 

The Ex d housing must not be opened! 

 

When  operated  in  hazardous  atmosphere,  the  sensor  head  must  be  connected  to  the  exLink 
counterpart or to a certified connection box. 

 
Disregarding these recommendations may compromise the Ex protection and result in a danger for 
personnel and assets.
 
 
 
 
 
 
 
 
 
 

This instruction is for quick orientation!  

Prior to installation and operation please download and read the detailed 

manual. Manuals in several languages are accessible on our homepage 

www.compur.com. 

 

Содержание Statox 560

Страница 1: ...s parts may be used The Statox 560 must not be connected to mains The supply voltage is 24 16 30 VDC All outputs of the Statox 560 may only be operated with 30 VDC Damaged or modified sensor heads mus...

Страница 2: ...e Statox 560 sensor head in upright position to the wall Use two M8 screws and suitable washers Compur Monitors offers an Ex e rated terminal box art 562988 made of varnished cast aluminum Picture 1 S...

Страница 3: ...o higher voltages or short circuiting the outputs may destroy it Picture 2 Statox 560 cable tail connection Caution A Connect the grounding contact to the ground of the building using a cable diameter...

Страница 4: ...e user and can be connected to a junction box if necessary The eXLink can be connected and disconnected in hazardous areas without hot work permit Picture 3 Connection of the eXLink Wire Function Desc...

Страница 5: ...ply 16 30 VDC 2 0 VDC Power supply ground 3 I_OUT 0 22 mA Current output 4 I_OUT Current output ground 5 Remote Self test Remote self test trigger 6 GND_R Common ground for relays 7 Maintenance Reques...

Страница 6: ...ing ring must be clean The warm up procedure see picture 6 can take some minutes especially with 3 electrode sensors After the warm up the Statox 560 will go into the measuring mode The following sett...

Страница 7: ...ce flashing yes yes Measuring mode Firmware 01 02 2016 06 16 10 33 Sensor detected NO SENSOR Loading Parameter COCL2 50 0 ppm Version 02 3 01 Sensor No 19718 b b w 3 2016 Warm up Please wait Please wa...

Страница 8: ...6 06 16 08 32 Service Output 2 mA Function Test Maintenance Request Short description Prooftest start Self test start set self test schedule Sensor calibration Sensor module replacement Error Code inf...

Страница 9: ...F flashing ON passive passive passive active Self test Monitoring 4 20 mA 7 Self test OFF OFF flashing ON passive passive passive passive Service Mode password protected 2 4 mA 1 Service menu OFF OFF...

Страница 10: ...Ohm EMC EN 61000 6 4 2007 A1 2011 EN 50270 2015 type 2 Functional safety SIL 2 compliant according to IEC 61508 2010 Automatic self test every 24 hours time is selectable Weight ca 4800 g Dimensions...

Отзывы: