PRODUCT IDENTIFICATION 

 
All pressurisation units described in this manual automatically maintain a minimum set pressure, the “Cold Fill” 
pressure, in a heating or chilled system by transferring make-up liquid from a breaktank or sealed vessel into the 

system. 
When the system pressure falls below the required level the Duty pump automatically refills the system until the 
pressure is restored. If the Duty Pump fails to maintain the required pressure the Support pump (where fitted) will 

operate in addition to the Duty Pump. 
 

Please note that the Serial Number “WNxxxxx” or “SNxxxxx” and model reference will be visible on the unit’s label and 
on the back page of the manual supplied with the unit. 

Examples of units manufactured by Aquatech Pressmain are shown below: - 

Please note: it is also possible for the pump/controls/tanks to have been sold as a separate item, in which case the 

O&M manual and CE declaration may only be applicable in part. 
 
Model number examples: - 

 

   

 

 

 

MiniPack 

MPxx-B 

     MiniPack 

MPxx-E 

 

Pressurisation unit with 

B

asic controller 

 

 

Pressurisation unit with 

E

nhanced controller 

 

MP 

 

 -  MiniPack 

MP 

 

 

 

 

 

 

 

3   

 

 

max 3.0Bar cold fill pressure 

 

7   

 

 

max 7.0Bar cold fill pressure 

 

 

1     1 

pump 

 

 

2     2 

pump 

 

 

 

 

B

asic MPC controller 

 

 

 

 

E

nhanced 2020+ controller 

 

 

 

 

 

 

e.g. 

MP31-B

 = max 

3

.0Bar cold fill pressure with 

1

 pump and 

B

asic MPC controller. 

 
 
 

A “standard/basic” –B pressurisation unit controller has a 2 digit 
display: - 
 
 

An “Enhanced” –E controller with BMS volt free relays has 
a 2 line by 20 or 24 character display: - 
 

 

 

2.3 

PRESSURE SYSTEM  IS  O.K. 
Pressure   

2.3 bar 

Содержание MINIPACK MP Series

Страница 1: ...ESSURISATION UNITS WITH MICROPROCESSOR CONTROLS MODELS MP31 32 71 72 ISSUE 6 30 01 2019 Head Office AGM House London Rd Copford Colchester Essex CO6 1GT UK Tel 01206 215121 Email aftersales agm plc co...

Страница 2: ...e manual supplied with the unit Examples of units manufactured by Aquatech Pressmain are shown below Please note it is also possible for the pump controls tanks to have been sold as a separate item in...

Страница 3: ...NG MiniPack Standard Basic B or Enhanced E UNITS 12 1 3 6 ELECTRICAL 12 2 USER INSTRUCTIONS 14 2 1 CUSTOMER ASSURANCE 14 2 2 COMMISSIONING 15 2 3 OPERATING INSTRUCTIONS 15 2 3 1 ADDITIONAL CAUTIONS 15...

Страница 4: ...PSSR and the Owner User should be made aware of their responsibility for this see section 3 Servicing Failure to install operate use maintain the equipment as recommended below could cause damage to...

Страница 5: ...or property 0 1 12 Pump motors with lifting eyes the lifting eyes are only suitable for lifting motors NOT the entire pump assembly This could cause injury to people or property 0 1 13 Ensure the bas...

Страница 6: ...ssure safety device into the system with due respect to the suction pressure present on the pumpset the pump closed valve pressure stated on the pump the maximum working pressure stated on any of the...

Страница 7: ...3 8 Ensure pumpset has an adequate water supply at all times to prevent dry running causing pump seal damage and water leakage 0 3 9 Do no attempt to start pumps without liquid in volutes pumps must b...

Страница 8: ...the suction side of the circulating pump but not within any influences from the circulating pump and for a heating system at the point of lowest temperature i e before the boiler If the equipment is...

Страница 9: ...stem Connection i The unit must be connected with any expansion vessels and cooling vessels to the underside of the return header on the suction side of the circulating pumps and boiler chiller see Lo...

Страница 10: ...mm Float Valve 15mm Incoming Mains Supply Microprocessor Controller System connection on suction side of Circulating Pumps Sytem filling device e g quick fill loop check local water regulations Drain...

Страница 11: ...r charge filling valve top and the diaphragm bottom on 70 C vessels top on 100 C vessels are accessible for future maintenance All vessels must have isolating and drain off valves fitted to enable the...

Страница 12: ...et terminal on pcb card in series with the boiler chiller control circuits so that in the event of a fault condition occurring the boiler chillers shut down and remain inoperative until the fault cond...

Страница 13: ...6a Typical standard B controller Wiring Diagram Fig 1 6b Typical Boiler wiring by others PCB1 PCB2 PCB3 O Keypad 2020Plus controller Pump 2 Auto Off Hand Pump 1 Auto Off Hand Display Pressure fault n...

Страница 14: ...urance does not apply to those items not supplied by us or to defects arising from parts not made or approved by AquaTech Pressmain The individual manufacturers own policies for dealing with defects w...

Страница 15: ...82 C or boiler power up to 1000kW READ GENERAL SAFETY INFORMATION 0 0 WARNINGS 0 1 and CAUTIONS 0 2 0 3 0 4 2 3 1 ADDITIONAL CAUTIONS 2 3 1 1 Isolate the pressurisation unit from the system before dra...

Страница 16: ...tted their sequence is automatically rotated either by starting the pump that has been idle the longest and or by timed operation dependent upon unit type Indicator lights where fitted on the fascia s...

Страница 17: ...is value High pressure delay time before alarm is initiated Duty delay to delay duty pump starting to circulator pump pressure dips Support delay to delay support pump starting in normal operation pre...

Страница 18: ...ched off for a long period a turbine pump where fitted may have seized Switch off unit insert flat blade screwdriver into slot on end of motor shaft and rotate pump until free Replace fuse with T1Ax20...

Страница 19: ...d signal present Check electrical supply is within tolerance or missing phase Pump seized motor failed Motor thermistor overheated No water in feed tank water level below supply tank low water alarm p...

Страница 20: ...ocedure shown below to avoid damaging rupture of the internal diaphragm and consequences of E g High and or low pressure problems unstable pump operation 2 To adjust air charge pressure 4 0Bar isolate...

Страница 21: ...s specialist fields are Pressure booster equipment and sealed systems for heating and chilled water distribution systems Regular servicing of any plant for essential services is vital because wear and...

Страница 22: ...A AquaTech Pressmain AGM House London Rd Copford Colchester Essex CO6 1GT UK Telephone 01206 215121 OPERATING PARAMETERS SERIAL No MODEL MP THE SERIAL MODEL NUMBERS MUST BE QUOTED WHEN REQUESTING ASS...

Отзывы: