Page - 13
1.3 Electrical
DANGER
Failure to heed the following will result in injury or death.
l
Deactivate power while routing wiring to control board.
l
Follow all National Electric Codes (NEC) and/or State and Local guidelines.
WARNING
Failure to heed the following may result in injury or death.
l
The information contained in this section is intended for use by qualified electricians familiar with electrical
service-industry safety standards and methods.
l
Locate the equipment disconnect as near to the heat pump as possible. Always satisfy applicable codes and
standards.
l
Never mount power-disconnects directly to the heat pump.
l
In sizing power wiring, be especially aware of up-sizing requirements necessary due to wiring distances. Always
satisfy applicable codes and standards.
l
AquaCal
®
heat pumps are designed to use copper conductors, only. Do not use aluminum wire.
l
If multiple heat pumps are on-site, confirm that the multiple heat pump configuration has been utilized. See
"
Connecting Multiple Heat Pumps (Optional)
" on page 25. This will prevent multiple heat pumps attempting to
start at the same time, causing an excessive power drop at start-up.
Additional Adjustments
Additional information on electrical adjustments have been provided in the appendix of this document
including:
1.3.a Electrical Requirements
Standards
Standards
Title
NFPA 70, Nat'l Elec.
Code 2017
The electrical installation must conform to the current
version of the National Electric Code (NEC), and all
applicable local and state codes
IEC 60335-1
Household and similar electrical appliances - Safety -
General Requirements
IEC 60335-2
Household and similar electrical appliances - Safety –
Particular requirements for electrical heat pumps, air-
conditioners, and dehumidifiers
UL 1995 & CSA C22.2
No. 236-15
Standard for Safety - Heating and cooling equipment
Table 1 - Standards
Grounding and Bonding
Follow local code requirements for proper grounding and bonding of heat pump equipment.
A bonding lug has been provided on the heat pump.
l
A bonding lug has been provided on the lower left hand corner of the plumbing access panel.
1
-
Ins
ta
lla
tion
Содержание SunPower SP05
Страница 2: ......
Страница 70: ...Page 66 Water Source WS10 Water Source WS03 WS05 SunPower SP05 2 Appendix ...
Страница 76: ...Page 72 l Follow all National Electric Codes NEC and or State and Local guidelines 2 Appendix ...
Страница 77: ...Page 73 2 Appendix ...
Страница 79: ...Page 75 2 10 Menu Trees 2 Appendix ...
Страница 80: ...Page 76 2 Appendix ...
Страница 107: ......
Страница 108: ......