ELECTRONIC CONTROL PANEL 

will display actual Pool or Spa water temperature for six 

seconds and then display mode of operation (HEA, COL, AUt or OFF) for two seconds. 

 

         

 
 
 
 
 
 
 
 
 
 
 
 
 
 

MODE SELECTION 

Selecting the desired mode of operation is accomplished by pressing the SELECT KEY. 
 

OFF MODE 

Press the SELECT KEY until you reach OFF.  Pressing the UP or DOWN key will allow you to 
enter either 

oFF

 or 

on

 mode. When in OFF Mode the display will show actual water temperature 

for six seconds and then display OFF for two seconds. 
 

Temperature Setpoint 

 Temperature set point maximum for POOL mode is 95

°

F (35

°

C). 

 Temperature set point maximum for SPA mode is 104

°

F (40

°

C). 

To change the temperature set point, press the SELECT KEY until you reach either POOL or 
SPA.  Press either the UP or DOWN key to scroll to your desired temperature set point.  Once 
your new temperature set point has been reached, release the UP or DOWN key.  Your new set 
point will be displayed for five seconds, then revert back to the actual pool or spa water 
temperature. 
 

Selecting Pool or Spa Mode 

Press the SELECT KEY until you reach P_S.  Pressing the UP or DOWN key will allow you to 
enter either POOL or SPA mode. LED indicator lights will verify the mode selected. 
 

HEAT & COOL MODELS ONLY: 

Selecting Heat or Cool or Auto 

Press the SELECT KEY until you reach PHC. Pressing the UP or Down key will allow you to 
choose P_H for Pool Heat, P_C for Pool Cool or AUt for Auto Mode. 

NOTE: UNIT WILL ONLY 

COOL IN THE POOL MODE. 

DIGITAL DISPLAY 

Displays actual Pool/Spa 
temperature. In select mode 
displays other parameters. 

SELECT/SERVICE KEY 

Used to select mode of 
operation and enter service 
mode. 

POOL LED

 

indicates pool mode. 

ON LED

 

indicates compressor is on. 

SPA LED

 

indicates spa mode. 

 INCREASE KEY 

  
DECREASE KEY 

Содержание ACT-1100T5S ACT-1250T6S

Страница 1: ...ELECTRICAL CONNECTIONS 4 WIRING DIAGRAMS 5 ELECTRONIC CONTROL PANEL 6 OPERATING YOUR HEAT PUMP 6 START UP 7 MAINTENANCE 8 WINTERIZING 9 TROUBLESHOOTING 9 CALLING FOR SERVICE 10 SYSTEM OPERATING SPECS...

Страница 2: ...be located outdoors Minimum of 24 of clearance on access service side of heater Minimum of 18 of clearance on all three air intake sides of heater Minimum of 48 of clearance for air discharge top of u...

Страница 3: ...3 WATER FLOW CONNECTIONS...

Страница 4: ...ctly to the electrical enclosure will ensure a moisture tight seal extending the life of the heater 5 Attach grounding conductor to the ground lug provided inside the electrical enclosure labeled 6 In...

Страница 5: ...terminals labeled POOL SPA on the bottom right of the electronic control board In the case of a remote thermostat where the temperature will be regulated externally set the POOL MODE to the OFF positi...

Страница 6: ...croll to your desired temperature set point Once your new temperature set point has been reached release the UP or DOWN key Your new set point will be displayed for five seconds then revert back to th...

Страница 7: ...continuously for at least 24 hours or more depending on the following factors Temperature difference between actual water temperature and desired water temperature Size of pool Ambient air temperature...

Страница 8: ...water flow to the heater is interrupted during the heating mode the internal water pressure switch will shut down the unit When normal water flow resumes the heater will automatically restart itself...

Страница 9: ...the heater to run Check to make sure the evaporator coil has enough clearance and that there are no restrictions to its airflow Certain ambient air conditions may cause the heater to go into defrost m...

Страница 10: ...sensor wiring or defective sensor DEF Heat pump in defrost cycle CALLING FOR SERVICE Visit www aquacomfort com click Service and complete the Service Request form Please eliminate any water flow prob...

Страница 11: ...arge Pressure psi Suction Pressure psi Superheat F ACT 750T4S 340 350 150 160 8 12 ACT 1100T5S 330 340 150 160 8 12 ACT 1250T6S 315 325 140 150 12 16 ACT 1500T7S 315 325 140 150 12 16 ACT 1750T7S 315...

Страница 12: ...ntenance and electrical service H Units sold outside the continental United States SERVICE PERFORMED WITHIN THE WARRANTY PERIOD must be approved by ACT PRIOR to service being performed and must be per...

Страница 13: ...____________________________________________________ City State _______________________________________________ Zip 4 _______________ Installation Date _________________Dealer ________________________...

Отзывы: