MODEL 76 – CRAWL SPACE CONTROL AND WIRING
NOTE:
Use 18-22 AWG wire for control wiring .
Used as a crawl space control (or remote control),
the Model 76 is mounted in the living space while
the dehumidifier is located in the crawl space .
When the dehumidifier is powered, the display on
the dehumidifier control will show “REMOTE” to
indicate that a remote control is being used . The
RH shown on the Model 76 is the RH measured at
the dehumidifier .
NOTE:
Air Cycling is not an option when using a
Model 76 as a remote control .
+ - A B
ODT
Sensor
Remote
Gh
Rf
Cf
Gs
Y
W
HV
AC EQUI
P.
DH
DH
R/+
C/-
B
A
MODEL 76 CONTROL
FIGURE 7 – Model 76 Crawl Space/Sealed Attic (Remote) Wiring
90-1860
AIR CYCLING
The dehumidifier has an optional ventilation feature that can be used to circulate air through the dehumidifier, to promote uniform humidity
levels throughout the space . When this feature is enabled, the dehumidifier fan can be set to run from 0 minutes (no air cycling) to 60 minutes
(continuous) per hour . See
VENTILATION / AIR CYCLING
in the
SYSTEM SET-UP, CHECK & START-UP
section on page 7 .
NOTE:
The on-board control must be used when Air Cycling .
5