LOCATION CONSIDERATIONS
6"
13"
ELECTRICAL
SERVICE ACCESS
THIS SIDE
MINIMUM
CLEARANCE
FOR PROPER
AIR FLOW
8 FT. POWER CORD
FILTER
MINIMUM
CLEARANCE
FOR FILTER
TOP VIEW
FIGURE 3 – Filter Access Clearance
90-2304
• Allow sufficient clearance for filter removal and
to prevent airflow obstruction
• Electrical service access will require the removal
of the side panel shown . Allow sufficient space
for service on this side of the unit .
0.38" MIN
2.00" MAX
3/4" FNPT DRAIN
INSTALLATION
LEVELING
DUCTWORK INSTALLATION
The feet can be adjusted to level the unit, and
if required, to accommodate drain fittings and a
secondary condensate pan .
Leveling is required
to ensure proper drainage from the dehumidifier .
See
Figure 4
.
Adding 5-10 feet of insulated ductwork to the inlet and outlet of the dehumidifier will ensure dehumidified air is circulated throughout the crawl
space and will reduce the noise level of the dehumidifier . Point the inlet and outlet ducts in opposite directions to minimize recirculation of
dehumidified air .
• Maximum recommended total duct length is 100 feet .
• To avoid pulling in dirt and other particles, do not lay intake duct on the floor of the crawl space .
NOTE:
This dehumidifier is designed for crawl space and stand-alone applications only .
Do not
duct to HVAC system .
FIGURE 4 – Level the Unit
90-2305
3