Configuration Settings
(Pre-Programmed to Factory Defaults)
Step 1CS
Press
▲
and
▼
simultaneously for 5 seconds and release. If screen in Step 2CS does
not appear, the lock on the valve is activated. To unlock press
▼
, NEXT, REGEN,
▲
in
sequence, then press
▲
and
▼
simultaneously for 5 seconds and release.
Step 2CS
Choose 2.0 (for 2” valve). Press NEXT to go to Step 3CS.
Press REGEN to exit Configuration Settings.
Step 3CS
Choose “FL2.0”.
(The setting chosen in this step will have no effect on non-metered valves.)
Press NEXT to go to Step 4CS. Press REGEN to return to previous step.
Step 4CS
Select between “28” Day and “7” Day regeneration program. 28 day will regenerate on
the days-intervals specified in futures steps, and 7 Day will regenerate on specific day(s)
of the week. Press the
▲
or
▼
buttons to scroll through the options until the correct
display is shown.
(Choose “28” or “7” without the “
◄
” indicator displayed next to “Volume”.)
Water Conditioner is set to “28 Day” as default.
See “Installer display settings” to adjust the frequency of backwash.
Press NEXT to go to Step 5CS. Press REGEN to return to previous step.
Step 5CS
Press
▲
or
▼
to select “DELY”
Press NEXT to go to Step 6CS. Press REGEN to return to previous step.
Step 6CS
Press
▲
or
▼
to select “OFF” option.
Note: If a setup utilizing a No Hard water Bypass (purchased separately) or “Separate Source”
during the regeneration cycle, choose the appropriate option in this step. See detailed instructions
on the next page.
Press NEXT to go to Step 7CS. Press REGEN to return to previous step.
Step 7CS
Press
▲
or
▼
to set external pressure differential option the desired setting:
“oFF” should be selected if no dP switch is connected
If dP is connected choose from “on0”, “dELy”, or “HoLd”.
See detailed instructions on the following page.
Press NEXT to exit configuration settings. Press REGEN to return to previous step.