40411 - Fail Safe
Sets the output condition (Input Registers 30300 and 30301) that the MPXI-F will revert to in the event of a
loss of signal condition.
0 = Disable (no fail safe output)
1 = 3.8 mA
2 = 22 mA
For Application Type (Holding Register 40402) 0 and disabled fail safe, Loss of Signal defaults to 20 mA.
For Application Type 1 - 11 and disabled fail safe, Loss of Signal defaults to 4 mA.
40408 - Sensitivity (Factory Calibrated)
Sets the level of gain that is applied to the returning float signal.
40409 - Pulses (Factory Calibrated)
Controls the duration of the signal being sent down the magnetostrictive wire.
40410 - Blanking (Factory Calibrated)
S
ets the blanking distance, which is the zone from the Zero Reference of the sensor to the point from which
the first signal will be valid. Signals from a float in the blanking area will be ignored.
40406 - Full Distance
Sets the positive distance (beginning from the sensor Zero Reference) to the point where the monitored
vessel is considered full.
40407 - Empty Distance
Sets the positive distance (beginning from the Zero Reference) to the point where the monitored vessel is
considered empty (usually the bottom of the stem).
40405 - Maximum Distance (Factory Calibrated)
Sets the distance (beginning from the Zero Reference) to the point where the sensor will stop looking for
float signals, usually the bottom of the stem. A float beyond the Maximum Distance value will not be detect
-
ed.