C.  SURFACE THERMOSTAT MODEL 

 

 

THREE PHASE TO SINGLE PHASE

 

1.  Disconnect blue wires from terminal L-2.

 

2.  Connect all blue wires to terminal L-1

 

 

(with black wires).

 

3.  Disconnect all red wires from terminal  L-3.

 

4.  Connect all red wires to terminal L-2 (with yellow wires).

 

5.  Incoming power will be connected to 

 

 

terminals L-1 and L-2 at job site.

 

 

D.  SURFACE THERMOSTAT MODEL 

 

 

SINGLE PHASE TO THREE PHASE

 

1.  Disconnect blue wires from terminal L-1

 

2.  Disconnect red wires from terminal L-2.

 

3.  Connect all blue wires to terminal L-2 (with yellow wires).

 

4.  Connect red wires to terminal L-3.

 

5.  Incoming power will be connected to 

 

 

terminals L-1, L-2 and L-3 at job site.

VI.   

 

CAUTION

Recheck all terminals for tightness, proper wiring per schematic,  and neatness of wiring,  Heater should 

be no less than factory constructed quality and appearance.

CHECK ALL WATER AND ELECTRICAL CONNECTIONS FOR TIGHTNESS

VII.  FINAL ASSEMBLY

 

A.  CONTROL PANEL

 

Replace foam door.  Cover all elements

 

and thermostats as originally constructed.  

 

Replace T & P valve package, close door, 

 

relatch and tighten the two control panel screws.

 

B.  RATING PLATE MODIFICATION

 

Following is a sample of the standard rating 

 

plate supplied on the front of the control panel 

 

door.

SURFACE THERMOSTAT MODEL 

SINGLE PHASE TERMINAL BLOCK

SURFACE THERMOSTAT MODEL

 THREE PHASE TERMINAL BLOCK

SAMPLE RATING PLATE

Содержание AITCE31-119

Страница 1: ...r S And Models A STCE31 50 80 119 A ITCE31 50 80 119 Commercial Electric Water Heaters CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROUGHLY BEFOR...

Страница 2: ...ar the electrical system of the heater Never touch electrical components with wet hands or when standing in water REQUIRED ABILITY CONVERSION OF ANY WATER HEATER LISTED IN THIS MANUAL REQUIRES ABILITY...

Страница 3: ...eting the unit conversion CONVERSION KIT NUMBER TABLE Models Allowed For Conversion Desired Input Conversion Kit No At Desired Voltage Total KW Element KW 208V 240V 277V 480V CSB or I S TCE models wit...

Страница 4: ...elements to appropriate storage bin C Open the appropriate conversion kit and remove the elements Check each element to ensure correct voltage and wattage D Install the new element starting it by hand...

Страница 5: ...HASE TO THREE PHASE 1 Disconnect blue wires from terminal L 1 2 Disconnect yellow wires from terminal L 2 3 Connect all blue wires and yellow wires to terminal L 3 4 Incoming power will be connected t...

Страница 6: ...L 3 5 Incoming power will be connected to terminals L 1 L 2 and L 3 at job site VI CAUTION Recheck all terminals for tightness proper wiring per schematic and neatness of wiring Heater should be no l...

Страница 7: ...HIPPING CRATE Close and tape the plastic flap on front of crate CHECK LIST All affected parts have been installed properly and have been checked for tightness All affected wires have been checked for...

Страница 8: ...SO WILL DAMAGE INTERNAL PARTS OHMS RESISTANCE TABLE VOLTAGE WATTAGE 208 240 480 2000 21 63 28 80 115 20 3000 14 42 19 20 76 80 4000 10 82 14 40 57 60 4500 9 61 12 80 51 20 5000 8 65 11 52 46 08 6000 7...

Страница 9: ...9 NOTES...

Страница 10: ...10 NOTES...

Страница 11: ...11 NOTES...

Страница 12: ...12 125 Southeast Parkway Franklin TN 37068 1 800 433 2545 apcom inc com...

Отзывы: