background image

AnyWireASLINK

 

4-8 

 Reference Example of Electric Wire 

 

Type 

Photo 

Specifications 

300V vinyl 
Cabtyre Cable 
(VCTF) 

 

JIS C3306 
Cross section area: 0.75 mm

2

 

Allowable power current: 7 A (30

C) 

Conductor resistance: 
25.1 

Ω/km (20

C) or less 

Insulation resistance: 

MΩ/km (20

C) or more 

Dedicated flat cable 
(HKV) 
Model:  FK4-075-100 

(100 m winding) 

 

Cross section area: 0.75 mm

2

 

Allowable power current: 7 A 
Maximum conductor resistance: 
25 

Ω/km 

Dedicated flat cable 
(HKV) 
Model:  FK4-125-100 

(100 m winding) 

 

Cross section area: 1.25 mm

2

 

Allowable power current: 12.7 A 
Maximum conductor resistance: 15 

Ω/km 

 

4.7 Transmission line supply current value 

 
AnyWireASLINK system can be established with two wires. 
Not only transmission signals but also power for the slave unit and whatever is connected to the load 
side of the slave unit are superimposed on these two wires. 
Allowable supply current (transmission line supply current value) from the transmission line varies 
depending on wire diameter and total wiring distance, therefore, it is necessary that the total 
consumption current of the connected DP-DN (consumption current of the slave unit  
consumption current on the load side connected to the 2-wire type slave) does not exceed this 
allowable power current value. 
 

 Transmission line supply current value 

Length of transmission line 

Wire diameter of transmission line (DP-DN) 

1.25mm

2

 

0.75mm

2

 

0.5mm

2

 

Total length: 50m or less 

MAX 2.0A 

MAX 1.2A 

MAX 0.8A 

Total length: Over 50m, no longer than 100m 

MAX 1.0A 

MAX 0.6A 

MAX 0.4A 

Total length: Over 100m, no longer than 200m 

MAX 0.5A 

MAX 0.3A 

MAX 0.2A 

 
 

Содержание B2G78-PN1

Страница 1: ...1 PMA 18204AA UMA 20010AC EN AnyWireASLINK System PROFINET Gateway B2G78 PN1 User s Manual Version 1 1 July 22 2019 Anywire Corporation AnyWireASLINK System...

Страница 2: ...e CPU unit Safety precautions ranks the safety precaution items into WARNING and CAUTION In addition Matters described in CAUTION may lead to serious consequences depending on the situation All descri...

Страница 3: ...Improper installations may cause malfunctions failures and or falls If they are to be installed on a DIN rail ensure to orient the products so that the fixed hooks would be on top Holding them with th...

Страница 4: ...line is long power voltage for the remote slave unit may become insufficient due to voltage drop Therefore connect an external power source to ensure the specified voltage Do not turn on the 24 V DC p...

Страница 5: ...ause damage to the screws or unit resulting in dropping short circuit or malfunction Do not disassemble or remodel each unit Failure malfunction injury or fire may result Make sure to shut off all pha...

Страница 6: ...ference 4 12 5 I O data 5 1 5 1 PROFINET module Module 5 1 5 1 1 Input output data 5 1 5 1 2 Status inputs 5 2 5 1 3 Slave unit status input 5 3 5 1 4 Status details 5 4 5 1 5 Command output 5 5 5 1 6...

Страница 7: ...ck 10 1 10 2 Maximum transmission delay time 10 2 11 GSD file 11 1 12 Troubleshooting 12 1 12 1 Visual check 12 1 12 2 Check using input output data 12 2 12 3 LED state of this machine 12 3 12 4 LED s...

Страница 8: ...which BOX is not placed In addition Digital Link Sensor in which AnyWireASLINK sensing function and wiring saving function are incorporated is proposed This is a sensor directly connectable to the tra...

Страница 9: ...Atmosphere No corrosive gas Rated altitude 1 0 2000 m Pollution degree 2 2 or less 1 Do not use or store the AnyWire ASLINK equipment in an environment pressurized more than the atmospheric pressure a...

Страница 10: ...Transmission cable disconnection detecting function Transmission cable short circuit detecting function Transmission circuit drive power supply voltage drop detecting function ID address duplication n...

Страница 11: ...Specifications 2 3 2 3 Dimensional outline drawing Unit mm Circuit board guide DIN hook Circuit board guide...

Страница 12: ...cations 2 4 2 4 Name of each part LED display section Set switch Maintenance connector Unused Number of bits setting switch AnyWireASLINK terminal block PROFINET connector OUT PROFINET connector IN DI...

Страница 13: ...IN rail 2 Snap in the machine by pressing it against the DIN rail 2 How to detach from the DIN rail 3 Using a screwdriver or similar tool loosen the DIN hook on the lower part of the bottom surface by...

Страница 14: ...outputs OFF OFF OFF OFF 256 inputs 256 outputs Factory setting Do not set a switch other than those listed in the above table 3 2 SET switch This switch is used to clear error flags and perform the a...

Страница 15: ...LINK 4 1 4 AnyWireASLINK 4 1 System configuration The AnyWireASLINK system consists of a gateway slave units and other peripheral devices For output For input For input For output Terminator Slave uni...

Страница 16: ...ion I O points and the total current consumption for the transmission lines does not exceed the maximum allowable supply current Connection of slave units There are roughly two types of methods for co...

Страница 17: ...nel 4 4 Connection mode AnyWireASLINK Bus allows for various connections such as T branching multi drop tree branching star branching etc T Branching Method The T branching method is a connection meth...

Страница 18: ...es Conversion to a dedicated flat cable Multi drop method The multi drop method is a way to connect slave units directly to cables When applying this method neither new cables nor non cable connecting...

Страница 19: ...od The star branching method is a way to connect the master unit and lay cable radially from a certain branching point to connect the slave unit This method allows for bundling transmission channels e...

Страница 20: ...em can be established with only 2 transmission lines DP DN The 2 transmission lines DP DN support a maximum 200m length as a total extension See P 2 2 This total extension also includes the length of...

Страница 21: ...25 mm2 rated temperature 70 C Shield cable Since AnyWire has high noise resistance it is unnecessary to use a shield cable Note that an improperly grounded shield cable shielding may result in troubl...

Страница 22: ...nsmission signals but also power for the slave unit and whatever is connected to the load side of the slave unit are superimposed on these two wires Allowable supply current transmission line supply c...

Страница 23: ...terminator for 1 master unit must be connected at the very end of the trunk line When extending stay lines branched from the trunk line if the length of the stay lines is more than 40 m one terminator...

Страница 24: ...ntire system from the master driving power supply or power supply from the local power supply insert a filter Insert the ANF 01 regardless of installation method and distance when complying with CE St...

Страница 25: ...y side lines of DP DN 24 V and 0 V exceeds the total length of 50 m 2 wire terminal 4 wire terminal 4 wire terminal 2 wire terminal 2 wire terminal General purpose power supply filter Use if necessary...

Страница 26: ...t by using a dedicated address writer ARW 04 or ARW 03 Bit address 255 or 511 showing that the address has not been set is set before shipment Address before shipment differs depending on the slave un...

Страница 27: ...6 215 214 213 212 211 210 209 208 239 238 237 236 235 234 233 232 231 230 229 228 227 226 225 224 255 254 253 252 251 250 249 248 247 246 245 244 243 242 241 240 Module name ASLINK bit output address...

Страница 28: ...rite command P OFF ON If the parameter write command P was OFF after a parameter write operation H Automatic address recognition flag During the process of automatic address recognition Automatic addr...

Страница 29: ...Status data 48 Parameter value 48 Slave unit status 49 64 L Status data 49 Parameter value 49 L Status data 50 Parameter value 50 L Status data 64 Parameter value 64 Name ON condition OFF condition L...

Страница 30: ...t status Meaning ON Slave unit voltage drop OFF No error 2 Sensing level status Bit status Meaning ON Sensing level drop OFF No error 3 I O disconnection Bit status Meaning ON I O disconnection OFF No...

Страница 31: ...ss recognition command in the ASLINK system Switching this bit from OFF to ON executes the automatic address recognition process P Parameter write command Switching this bit from OFF to ON writes the...

Страница 32: ...ated parameter number 34 R Q Designated ID 48 Designated parameter number 48 ID and Param Num 49 64 R Q Designated ID 49 Designated parameter number 49 R Q Designated ID 50 Designated parameter number...

Страница 33: ...68 7 I68 6 I68 5 I68 4 I68 3 I68 2 I68 1 I68 0 I69 7 I69 6 I69 5 I69 4 I69 3 I69 2 I69 1 I69 0 IW70 IB70 IB71 I70 7 I70 6 I70 5 I70 4 I70 3 I70 2 I70 1 I70 0 I71 7 I71 6 I71 5 I71 4 I71 3 I71 2 I71 1...

Страница 34: ...I O data 5 8 Input output data...

Страница 35: ...mation flag R P 5 6 Step 6 Ensure that the update confirmation flag return signal L is updated to the value written in Step 5 P 5 3 Step 7 If the update confirmation flag and the update confirmation f...

Страница 36: ...5 5 Step 6 Ensure that the parameter write in progress flag G is ON P 5 2 Step 7 Switch the parameter write command P from ON to OFF P 5 5 Step 8 Confirm that the parameter write in progress flag G ha...

Страница 37: ...the pin assignment was correct when the link connector was crimped Check that external power supply is correctly connected to the terminal block Also pay attention to short circuit incorrect wiring a...

Страница 38: ...no incorrect wiring or insufficient tightening of the screws When newly creating a system or alternating the system adding or eliminating slave units changing addresses perform automatic address recog...

Страница 39: ...lave units and addresses match those of the actual system 304 130 Parameter access error Occurrence ID is stored Check for any effects by noise 305 131 Slave unit status error Occurrence ID is stored...

Страница 40: ...cognition Procedure 1 Check that all of the slave units operate normally 2 Keep pressing the SET switch on this equipment until the SET LED green lights 3 After a while the SET LED will turn off Then...

Страница 41: ...recognition has been executed with the system The new slave unit supports the single unit simplified replacement function 1 The new slave unit corresponds to the factory set address Procedure 1 Discon...

Страница 42: ...ected before an undesignated ID is detected A case where an unidentified ID is included in the IDs that have been registered in the system through automatic address recognition A case where the newly...

Страница 43: ...response from slave unit Flashing w 1 second interval DP DN short circuit Flashing w 0 2 second interval 24V DC not supplied or low voltage OFF Normal operation MS_G Module Status LED Green Green ON...

Страница 44: ...or Flashing single flash Station name error Flashing Double flashes IP address error Flashing Triple flashes Configuration error OFF Offline Power supply is OFF Link Activity PROFINET Link status indi...

Страница 45: ...ector type MC1 5 5 STF 3 81 manufactured by PHOENIX CONTACT Ground the LG terminal via a low impedance cable 50 cm or shorter For fastening a screwdriver having a tip of approximately 0 4 2 5 mm is re...

Страница 46: ...NET connectors 2 Insert the ASLINK connector terminal block and fasten two screws on both sides 9 3 2 Connector removal 1 Loosen the screws on both sides of the ASLINK connector terminal block and rem...

Страница 47: ...16 bit basis between this device and the higher order controller With double checking performed on a 1 bit basis however data cannot be guaranteed on a 16 bit basis in a strict sense Cautions in hand...

Страница 48: ...mission cycle time differs depending on how the number of transmission I O points is set up For more information refer to 2 2 Performance specifications 4 6 Processing time required by this device 0 6...

Страница 49: ...cation settings etc in the XML format During network configuration setting loading the relevant information into the PROFINET configuration tool can simplify the communication setting procedure Use th...

Страница 50: ...referring to the manual for the PROFINET master unit being used P 8 1 2 LED display on the AnyWireASLINK side Check the LINK LED The LINK LED is flashing Normal If the LED is unlit check that 24V powe...

Страница 51: ...error code P 5 2 2 Checking the error occurrence ID information The error occurrence ID is stored in the latest error occurrence ID P 5 2 3 Checking the status detail information If the error issued w...

Страница 52: ...rive voltage drop error Check items Description of measures Check the voltage of the 24 V DC external supply power Make adjustments so that the power voltage of the 24 V DC external supply power does...

Страница 53: ...Under normal conditions a voltage of approximately 20 V to 22 V is observed in the DC mode of a tester When the transmission line is disconnected etc the position can also be identified by a differenc...

Страница 54: ...Lot identification label 13 1 13 Lot identification label Lot No of this product can be identified with this label Lot identification label...

Страница 55: ...roducts 3 Any failure caused by modification or repair by a person other than the deliverer 4 Any failure caused by a natural disaster major accident etc and the deliverer side has no responsibility f...

Страница 56: ...RoHS 15 1 15 RoHS SJ T11364 2006 10 Pb Hg Cd Cr VI PBB PBDE SJ T11364 GB T26572 GB T26572 GB T15969 2...

Страница 57: ...unit simplified replacement function Additional description of 13 Lot identification label 1 1 July 22 2019 Corrections to 2 1 General specifications Corrections to 2 2 Performance specifications Cor...

Страница 58: ...Anywire Corporation Headquarters 1 Babazusho Nagaokakyo shi Kyoto 617 8550 JAPAN Website http www anywire jp E Mail inquiry info_e anywire jp...

Отзывы: