Specifications
2-1
2. Specifications
2.1 General specifications
Items
Specifications
Ambient temperature for use
0 to +55°C
Storage temperature
-20 to +75°C
Ambient humidity for use
10 to 90%RH (No condensation)
Atmosphere
No corrosive or flammable gas
2.2 Performance specifications
Items
Specifications
Transmission clock
27kHz (37
μ
s)
Transmission
distance/supply current
Wire
diameter
Transmission distance DP-DN
allowable
supply current
1.25mm
2
Shorter than 50m
Less than 2A
Exceeding 50m, shorter than 100m
Less than 1A
Exceeding 100m, shorter than 200m
Less than 0.5A
0.75mm
2
Shorter than 50m
Less than 1.2A
Exceeding 50m, shorter than 100m
Less than 0.6A
Exceeding 100m, shorter than 200m
Less than 0.3A
Number of units
connected
Up to 128 units
Transmission method
DC power supply superimposed total frame/cyclic method
Connection mode
T-branch method, multi-drop method, star-branch method, tree-branch
method
Transmission protocol
AnyWireASLINK protocol
Error control
Double check, checksum
Connection I/O points
Up to 512 points (Input 256 points/output 256 points)
RAS function
Transmission line disconnection detection function, transmission line
short-circuit detection function, transmission circuit drive power voltage
drop detection function, ID (address) redundancy/not set detection
function
Electric wire used
General-purpose two-wire/four-wire cable (VCTF, VCT 0.75 to
1.25mm
2
, rated temperature 70°C)
General-purpose electric wire (0.75 to 1.25mm
2
, rated temperature
70ºC)
Dedicated flat cable (0.75mm
2
, 1.25mm
2
, rated temperature 90ºC)
Power supply
Voltage 24[V] DC +15 to -10% (21.6 to 27.6[V] DC) Ripple 0.5[V]p-p max.
Current 150[mA] (when 128 slave units are connected, load current is not
included)
Transmission I/O point
number setting
Input 32 points
Output 32 points
Input 64
points
Output 64
points
Input 128
points
Output 128
points
Input 256 points
Output 256 points
Transmission cycle
time
2.4ms
3.6ms
6.0ms
10.7ms
Rated voltage
24V DC (21.6V to 27.6V)
Communication power
supply
Superimposed on transmission line
Load power supply
Local power supply or collective power supply
Vibration resistance
Conform to JIS C 0040
Withstand voltage
1,000V between external terminal and outer box for one minute
Noise resistance
1,000 Vp-p, pulse width 1
μ
s