Software functions
7-8
Error code
Name
Error occurrence
ID
Countermeasures taken by customer
DEC
HEX
303 12F Parameter
set
value error
Occurrence ID is
stored.
The slave unit has detected a signal for writing a
parameter which cannot be set to itself.
After narrowing down error IDs, check that the
set value of the slave unit parameter is within
the settable range.
304 130 Parameter
access
error
Occurrence ID is
stored.
Check for any problems due to noise.
305 131 Parameter
access
error
Occurrence ID is
stored.
The slave unit provides notification of error
status.
Check the details of the target unit status and
remove the cause of the fault.
400 190 ID
redundancy
error
Occurrence ID is
stored.
A redundant address (ID) is set for a connected
slave unit.
After narrowing down error IDs, check the
setting of the slave unit address (ID), and set the
ID so that there will be no redundancy.
401
191
ID not set error
Occurrence ID is
stored. (255 or
767)
There is a slave unit whose address has not
been set (default setting).
Perform the following:
Set the slave unit address.
Check that the slave unit address is not set to
255.
7.1.1.9 Redundant address (ID)
During automatic address recognition, a redundancy check is carried out on the registered connection IDs
(addresses) and the results are saved.
Up to 12 redundant IDs can be displayed.
The redundant ID (address) list is as follows.
Modbus/TCP address
Data
Memory
address
Offset address 15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
30309 308
Redundant ID1
30310 309
Redundant ID2
¦
¦
¦
30319 318
Redundant ID11
30320 319
Redundant ID12
The ID format is as follows:
15 14 13
12 11 10
9
8
7
6
5
4 3 2 1 0
Type
Address (0x00 to 0xFF)
Type: 00: Output, 01: Input (input/output mixed)
Description
0x000 to 0x0FF
Output slave unit
0x200 to 0x2FF
Input (input/output mixed) slave unit
Example: Output slave unit address 3 = 0x0003
Input slave unit address 10 = 0x020A