AnyWireASLINK
6-10
6.9 AnyWire filter
If any of the parallel lines of DP, DN, 24V, or 0V exceeds the total length of 50m in a power supply system to
be supplied, connect in series the "ASLINK filter [Type ANF-01]" or a "COSEL filter [Type EAC-06-472]" to
24V and 0V in the starting position of the parallel lines.
This will improve noise resistance, reduce the impact of crosstalk by transmission signals, and stabilize the
signals.
Insert a filter whether using a master power supply for the entire system or using a local power supply.
Filter allowable current
Model Type
Allowable
current
ASLINK filter
ANF-01
MAX 5A/24V DC
COSEL filter
EAC-06-472
MAX 6A/24V DC
ASLINK filter (ANF-01) connection example when there is a power supply to the entire system
When complying with CE Standards, insert the "ANF-01" regardless of installation
method and distance.
AnyWireASLINK master
General-purpose power
supply filter
(Use if necessary)
24V DC
stabilized
power supply
If any of the parallel lines of
DP, DN, 24V, or 0V exceed
a total length of 50m
Filter notation in the
drawing
For more details regarding the
ANF-01, please refer to the
ANF-01 Products Guide.
Two-wire terminal
Four-wire terminal