-BL296*B08F****V50 5/22-
The branching
has no limitation.
AnyWireASLINK
master
Black:
DN
Red: DP
Black: DN
Red: DP
Black: DN
Black: DN
Red: DP
Red: DP
Black: DN
Red: DP
2 points
2 points
2 points
2 points
2 points
2 points
2 points
2 points
2 points
8 points
8 points
24V DC
*
Black: DN
Red: DP
Black: DN
Red: DP
24V DC
*
*
Make sure to use a 24V DC
stabilized power supply for
the power supply to be
connected.
*
When complying with the
UL Standard, make sure to
use a 24V DC stabilized
power supply of “NEC
Class 2 Output.”
4P link connector is
convenient for
branching.
Dedicated flat cable
1.25mm
2
(4-wire)
The sum of the
portions of DP, DN is
the total line length.
1.25mm
2
0.75mm
2
MAX
2A
MAX
1.2A
MAX
1A
MAX
0.6A
MAX
0.5A
MAX
0.3A
0.5mm
2
MAX
0.8A
MAX
0.4A
MAX
0.2A
If the load current consumption
is large, a four-wire (isolated)
terminal can be selected.
This terminal can correspond
to I/O of the controller with an
external power supply.
■
Relationship between the size and length of
the transmission line and the supply current (Table 1)
Size of
the transmission
line (DP, DN)
Supply current on the transmission line (DP, DN)
Total length:
50m or less
Total length: Over 50m,
no longer than 100m
Total length: Over 100m,
no longer than 200m
CAUTION
- Refer to Table 1 so that the size and length of the transmission
line and the allowable supply current lie within an appropriate
range.
- Connect the same symbols (DP, DN) correctly between the
AnyWireASLINK master unit and each device.
- The branching length or branch number has no limitation.
- Include the length of the cable provided with the terminal in the
“total line length.”
- Connect the terminator (with polarity) to the DP, DN terminal
farthest from the AnyWireASLINK master unit.
[System Configuration Example]
[Installation Location]
- Locations where this product is not directly subject to vibration or shock
- Locations where this product is not directly exposed to dust
- Locations where this product is not directly exposed to conductors, such as metal chips or spatters
- Locations without condensation
- Locations where the atmosphere is free of corrosive gases, flammable gases, and sulfur
- Locations far from high-voltage or high-current cables
- Locations far from servos, inverters, and other cables and controllers that generate high-frequency noise
The AnyWireASLINK can employ a two-wire or four-wire terminal selectively depending on the load current.
If the load current is small, using a two-wire (non-isolated) terminal allows for achieving simplified wiring without local power supply.
In the case of prioritizing the sites of concentrated loads and/or the number of connections, hybridization with a four-wire (isolated)
terminal, which supports local power supply, is also possible.
Make sure to use a four-wire (isolated) terminal in the case of input and load driving using an external power supply.
[How to Connect AnyWireASLINK]
AnyWireASLINK terminator
One terminator should be connected to the DP, DN terminal farthest
from the AnyWireASLINK master unit.
Connect it correctly so as not to set the wrong polarity.
General-purpose power supply filter
General-purpose
power supply filter
ASLINK filter