35 (136)
2.
The Error Register (object entry 1001h) is set with the corresponding bit information
Bit
Description
Condition for setting bit
0
Generic error
Always set when another error bit in this object is set.
1
Current
Event code is 20h - 23h
OR
Event code is FFh AND the high byte in NW specific information
is 20h - 23h.
2
Voltage
Event code is 30h - 33h
OR
Event code is FFh AND the high byte in NW specific information
is 30h - 33h.
3
Temperature
Event code is 40h - 42h
OR
Event code is FFh AND the high byte in NW specific information
is 40h - 42h.
4
Communication error
Event code is 80h - 82h
OR
Event code is FFh AND the high byte in NW specific information
is 80h - 82h
OR
Anybus state equals ERROR.
5
Device profile specific
Always 0
6
Reserved
Always 0
7
Manufacturer specific
Event code is FFh
AND
the high byte in NW specific information is FFh.
3.
If the diagnostic instance is created in the state WAIT_PROCESS or higher, an EMCY object is sent to
the network with the following information:
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
00h
Event
Code
Error
Register
(1001h)
Manufacturer Specific Field (Not used)
No EMCY object is sent if the instance is created in either of the states SETUP or NW_INIT.
When creating a Major unrecoverable event, this will not end up as an EMCY message on the bus, since
this effectively forces the Anybus module to enter the EXCEPTION state.
Bytes 0 and 1 (00h + Event Code) will be replaced by the value of attribute 3 if implemented.
An EMCY object with error code 0000h (“error reset”) is sent when a diagnostic instance is deleted.
Anybus
®
CompactCom
™
40 EtherCAT
®
Network Guide
SCM-1202-034 1.1