About the Module
10
Doc.Id. SCM-1200-121
Anybus Communicator CAN to CANopen
Doc.Rev. 1.00
2.3 Status LEDs
The status LEDs on the front indicate the status of the module as shown in the table below.
Status LEDs 1 - 4 indicate the status of the CANopen network and status LEDs
5 - 6 indicate the status of the CAN subnetwork and the device.
#
State
Status
1 - Run
Off
No power
Single flash, green
Stopped
Blinking green
Pre-operational
Blinking red
Bus initialization fault
Green
Operational
2 - Error
Off
No error
Single flash, red
Warning limit reached
Double flash, red
Error Control Event
Triple flash, red
Sync Error
Red
Bus off
3 - Status
Off
Normal operation
Red
Unrecoverable fault detected
4 - Power
Off
No power
Green
Power
5 - CAN subnet-
work status
Off
Power off/no CAN communication
Green
Running with no transaction error/timeout
Flashing red
Transaction error/timeout or subnetwork
stopped
Red
Fatal error
6 - Device status
Off
Power off
Alternating Red/Green
Invalid or missing configuration
Green
Operation mode Run
Flashing green
Operation mode Idle
Red
Fatal error