The female and male connectors cannot be installed
incorrectly. Hold the connection in place with one spanner
and tighten the female connector with the other,
otherwise the connection can be damaged.
1. Connect the pipes in the installation kit to the connections
on the indoor unit.
– Align and tighten the connections by hand and then
tighten them with the spanners.
2. Fully tighten the connection without stopping. A hissing
noise can be heard. Hold the connection in place with one
spanner and tighten the female connector with the other
spanner.
– Tighten to 18 Nm. Use a torque wrench to be exact.
– Never turn the fixed pipe connections. Only use the
spanner as a counterhold when connecting. Without a
counterhold the connections can warp, which can ruin
them.
3. Retighten the connections 24 hours after the installation has
been completed.
FIG. 38
Connect the installation kit to the outdoor unit
NOTE:
•
The pipe ends in the installation kit have female and male
connectors for connection to the fixed pipe sections on the
outdoor unit.
•
The female and male connectors cannot be installed
incorrectly. Hold the connection in place with one spanner
and tighten the female connector with the other,
otherwise the connection can be damaged.
1. Connect the installation kit's pipes to the connections on the
outdoor unit.
– Align and tighten the connections by hand and then
tighten them with the spanners.
2. Fully tighten the connection without stopping. A hissing
noise can be heard. Hold the connection in place with one
spanner and tighten the female connector with the other
spanner.
– Never turn the fixed pipe connections. Only use the
spanner as a counterhold when connecting. Without a
counterhold the connections can warp, which can ruin
them.
– Retighten the connections 24 hours after the
installation has been completed.
FIG. 39
ELECTRICAL CONNECTION
FIG. 40
NOTE:
•
Never connect the power supply to the heat pump before
all the connections are finished and all the safeguards are
refitted.
Indoor unit
1. The heat pump connects to the mains with a standard cable
and does not require any alteration to the electrical system
in the building.
Outdoor unit
1. Unscrew and remove the cover on the outdoor unit’s
junction box.
2. Plug in the plug and fasten the cable in the holder.
Содержание 416120
Страница 3: ...1 2 4 5 3 5 6 7 1 2 3 4 9 8 10 11 12 13 14 15 16 22 17 18 19 21 20...
Страница 5: ...8 50 C 11 12 13 14 15 SET TEMP Temp Max temp 9...
Страница 6: ...10 11 12 13 3 1 2...
Страница 7: ...14 15 1 2 3 4 1 2 3 4 6 5...
Страница 8: ...16 17 1 2 3 7 5 6 4 7 5 3 1 2 6 8 9 4...
Страница 9: ...10 8 4 6 5 1 2 3 9 7 11 12 18 19...
Страница 10: ...20 21 22...
Страница 11: ...28 29 30 23 24 25 26 27 T6 12 m 12 m T6 T6 T6...
Страница 12: ...31 32 33 34 Min 10 cm 37 35 36...
Страница 13: ...38 39 40...
Страница 22: ...SE 22 TEKNISKA DATA...
Страница 43: ...NO 43 TEKNISKE DATA...
Страница 64: ...PL 64 DANE TECHNICZNE...
Страница 86: ...EN 86 TECHNICAL DATA...