Commissioning
29
EN
Check gas Valve
Check water flow
Check water flow
The water flow through the boiler
can be checked with two different
methods shown below.
ΔT measurement
Check the temperature difference
over the boiler (ΔT flow-return)
when the boiler is running on 100%
load. The nominal ΔT is 20K and
must be at least between 10K and
30K for secure boiler operation. An
indication of the actual flow rate can
be found with the following calcula
-
tion (see table below for nominal
data):
Δp measurement
Check the pressure difference over
the boiler (Δp flow-return) when the
boiler pump is running (burner on is
not required).
The nominal Δp for each boiler type
can be found in the table below, ac
-
tual Δp must be within:
1.0*Δpnom. ≤ ΔP ≤ 4.0*Δpnom.
An indication of the actual flow rate
can be found with the following cal
-
culation (see table below for nomi
-
nal data):
Water flow data
SUPAflo EVO
SF61
SF62
SF63
SF64
SF65
SF66
SF67
Nominal flow rate
[m
3
/h]
6.1
8.1
10.1
12.2
16.3
20.4
23.1
ΔT at nominal flow rate
[°C]
20
Δp at nominal flow rate
[kPa]
11.2
26.8
31.2
11.9
32.3
34.3
57.1
qactual = √(Δpmeasured / Δpnominal) * qnominal [m
3
/h]
qactual = (ΔTnominal / ΔTmeasured) * qnominal [m
3
/h]
Gas valve
Due to the length of the chimney
system draft or a resonance can oc
-
cur. This draft can have a negative
impact on the ignition and stability
of the combustion. To reduce the
influence of the draft or to remove
the resonance the flue gas valve can
be adjusted. For this 10 positions
are available, several test on diffe
-
rent flue gas valves positions are to
be executed to find the optimal po
-
sition for the complete installation.
A
Содержание SUPAflo EVO SF60 EVO
Страница 1: ...INSTALLATION AND SERVICE MANUAL SUPAflo EVO Water Heater SF60 EVO...
Страница 2: ......
Страница 15: ...Installation 15 EN Disassemble the casing 7 8 9...
Страница 23: ...Installation 23 EN Wiring diagram Boiler...
Страница 46: ...Note 46 Note...
Страница 47: ...Note 47 EN Note...