Installation
18
Requirements and regulations
Regulations for the construction of
flue gas systems are very different
for each country. It should be en
-
sured that all national regulations
with regard to flue gas systems are
respected.
Pay attention to the following rec
-
ommendations when dimensioning
a flue gas system.
Only approved flue gas material may
be used.
The flue gas system must be prop
-
erly calculated to ensure a safe func
-
tioning of the system.
Flue gas system components should
be removable for maintenance pur
-
poses.
You have to take in consideration the
following material requirements.
Materials
Exclusively materials which are heat
resistant and resistant to flue gases
and aggressive condensate, and CE
approved may be used.
In particular for flue gas system see
the following data.
Air/Flue gas system
Plastic
PP*
Stainless
steel
Temperature
class:
T120
T250
Pressure
class
P1
P1
Corrosion
class:
W1
W1
* Use material with “E” reaction top
fire class, as minimum.
FLUE GAS DATA
Boiler
type
Nominal heat
output
Nominal heat
input
Flue
gas
connection
CO
2
Level
Flue gas tem
-
perature
Flue gas
quantity
Max
permissible
flue resistan
-
ce
SUPAflo
EVO
kW
kW
mm
%
°C
g/s
Pa
max
min
max
min
max
min
max
min
max
min
max
min
SF61
142.3 31.3 145.0 32.2
150
10.2
± 0.2
9.4
± 0.2
75
± 2
60
± 2
53.7
12.8
200
10
SF62
190.4 42.0 194.0 43.1
150
71.9
17.1
200
10
SF63
237.6 47.0 242.0 48.4
200
89.6
19.2
200
10
SF64
285.7 56.5 291.0 58.2
200
107.8 23.0
160
10
SF65
381.3 79.6 388.0 80.5
250
143.7 30.7
400
10
SF66
476.7 94.6 485.0 97.0
250
179.7 38.4
300
10
SF67
540.2 120.0 550.0 122.2
250
203.7 48.4
484
10
Содержание SUPAflo EVO SF60 EVO
Страница 1: ...INSTALLATION AND SERVICE MANUAL SUPAflo EVO Water Heater SF60 EVO...
Страница 2: ......
Страница 15: ...Installation 15 EN Disassemble the casing 7 8 9...
Страница 23: ...Installation 23 EN Wiring diagram Boiler...
Страница 46: ...Note 46 Note...
Страница 47: ...Note 47 EN Note...