This charger features user selectable 2 or 3 stage charging. The charging profile is selected by 

moving the slide switch on the front panel up to 3 stage or down for 2 stage charging. 

A two-stage charger provides a constant current until the battery reaches its rated capacity 

and then switches to a “float” voltage. The current then reduces as necessary to maintain 

the battery at the float voltage. The charger can be connected to the battery indefinitely and 

will provide the appropriate profile. A two-stage charger is recommended in most instances 

since it is the most versatile and can be permanently connected to attenuate the characteristic 

discharge of unused batteries. A load can be put on the battery or batteries without altering 

its ability to keep the battery at optimal charge.

100%

75%

50%

25%

0%

Bulk

(Constant Current)

Float

(Constant Volts)

Time

Two Stage Charge

Volts

Amps

100%

75%

50%

25%

0%

Bulk

(Constant Current)

Absorption

(Constant Volts)

Float

(Constant Volts)

Time

Three Stage Charge

Volts

Amps

2 or 3 Stage Charging

voltage at the output terminals of the unit with a good digital voltmeter. As shipped from the 

factory, the unit is preset to 13.6, 27.2, 36.3 or 54.4 VDC, which is generally recommended for 

lead-acid batteries. If you wish to adjust the charging voltage, remove the cover plate (secured 

by 2 screws) to expose the output adjust potentiometer.  Reach in with a very small flat blade 

screwdriver to rotate the potentiometer. Please note that this adjusts both the float and 

absorption voltages at the same time. Clockwise increases the output voltage, and counter 

clockwise decreases it. When you are done, replace the cover plate and securely tighten 

the screws. It is advisable to check with the battery manufacturer before changing the float 

voltage. 

Содержание BCD1000 Series

Страница 1: ...IES Battery Charger 8128 River Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 800 668 3884 US CANADA www analyticsystems com An ISO9001 and AS9100 Registered Company Battery Chargers In...

Страница 2: ...Copyright 2005 2014 Analytic Systems Ware 1993 Ltd...

Страница 3: ...wer switch to off position ALL BATTERY CHARGERS 1 WARNING RISK OF EXPLOSIVE GASES i i WORKING IN VICINITY OF A LEAD ACID BATTERY IS DANGEROUS BATTERIES GENERATE EXPLOSIVE GASES DURING NORMAL BATTERY O...

Страница 4: ...and recommended rates of charge xiii Add distilled water in each cell until battery acid reaches level specified by battery manufacturer This helps purge excessive gas from cells Do not overfill For...

Страница 5: ...be added factory option to allow monitoring of charg ing current and charging voltage Specifications Input Voltages Nominal ip 110 250 300 Actual Vdc 100 140 230 280 280 360 Input Amps max 14 8 6 5 5...

Страница 6: ...de an appropriate junction box Refer to the specifications table for the correct sizing of the circuit breaker in the distribution panel Red Positive Black Negative Designed and manufactured by ANALYT...

Страница 7: ...es will reach the float voltage at which time the charging light will go off and the charging current will reduce as necessary to maintain the batteries at that voltage You may check this OUTPUT CONNE...

Страница 8: ...al charge 100 75 50 25 0 Bulk Constant Current Float Constant Volts Time Two Stage Charge Volts Amps 100 75 50 25 0 Bulk Constant Current Absorption Constant Volts Float Constant Volts Time Three Stag...

Страница 9: ...icators to determine the cause of the shutdown CHARGING Indicates that the battery charger is charging the batteries If the LED is not on the batteries may be fully charged and the charger is supplyin...

Страница 10: ...ors then turn it off again Remove the eight screws holding on the cover Turn the unit upside down remove the cover and locate J22 It will be next to the relay as is shown in the above diagram Simply m...

Страница 11: ...remotely as well as duplicating all the diagnostic indicators and audible alarm REMOTE CONNECTOR This connector is located on the side of the unit Important To prevent the possibility of High Voltage...

Страница 12: ...er will charge the battery at approximately 10 of its normal rate i e 4 amps for a 40 amp charger until the battery reaches equalize voltage and then the current reduces as necessary to maintain the b...

Страница 13: ...the battery The sensor may be placed on top of the battery but it should be secured to the battery so as to prevent it from losing contact with the battery Battery Charger Temperature Compensation The...

Страница 14: ...p Components Conformal Dipping and RTV Compound Option w Wide Temperature Operation 40 to 55 C incl Option SM High Voltage Protection on the DC Input Side Option d Paralleling Diodes Option FI Forklif...

Страница 15: ...ng will incur additional charges and are the responsibility of the Purchaser 6 Analytic Systems reserves the right to void the warranty if a Labels identification marks or serial numbers are removed o...

Страница 16: ...Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 800 668 3884 US CANADA www analyticsystems com An ISO9001 and AS9100 Registered Company Battery Chargers Inverters Power Supplies Voltage...

Отзывы: