Triggering from EP1200A 

Emergency Paging Mic

24V Power supply for VC 

overriding

to volume controllers 

to volume controllers 

Link these ports

ALL  CALL  paging  can  be 

performed  from  Emergency 

Paging  Mic  (  EP1200A  ),  which 

when  Relay  Trigger  port  is 

energised,  it  shall  provide  a 

voltage  free  relay  contact. 

Connect  24V  DC  power  supply 

from  PSU  to  trigger  external 

volume  controllers  for  Overriding 

purpose.

When  multiple  ZS  are  used,  link 

the Relay Trig ports together, thus 

any triggering from EP1200A shall 

perform  ALL  CALL  paging  to  all 

zones at all the zone selectors.

Note :

Pressing ALL  CALL  at  individual 

zone selector shall only trigger all 

zones at the unit, without trigger-

ing the relay output ; ie. this shall 

not override the volume controllers

+

DC 24V

CON

RLY

TRIG

RLY

PR

ZS

PIN 8-COM

PIN 7-24V

PIN 6-Z6

PIN 5-Z5

PIN 4-Z4

PIN 3-Z3

PIN 2-Z2

PIN 1-Z1

+

DC 24V

CON

RLY

TRIG

RLY

PR

ZS

PIN 8-COM

PIN 7-24V

PIN 6-Z6

PIN 5-Z5

PIN 4-Z4

PIN 3-Z3

PIN 2-Z2

PIN 1-Z1

+

DC 24V

CON

RLY

TRIG

RLY

PR

ZS

Connecting Emergency Overriding Port

PAGE 6

ZS5601 / ZS5121 | ZONE SELECTOR

to  trigger  volume  controller 

overriding relay, etc.

TO VOLUME CONTROL OVERRIDING 

RELAY OR OTHER E/CY. INDICATOR 

OR EMERGENCY INTERFACE  

LOAD: 24V DC 2 AMPS

EMER. PAGING MICROPHONE 

SWITCH  OR  OTHER  EMER. 

TRIGGER

- VE

24V DV

(PS9400)

More than often, volume controllers are installed at areas that requires sound level to be attenuated, eg. conference room, 

etc.

Overriding is required when an emergency switch is pressed, normally via firemen paging mic with a dry contact. With 

the  connection  shown,  whenever  the  switch  is  pressed,  it  would  trigger  the internal  relay  which  shall  then provide a 

dry contact. It can be used to trigger overriding relay at volume controller or other external device such as emergency light 

indicator .  It can also be used to trigger ALL CALL.   

Please ensure the loading does not exceed the limits as indicated.  Polarity must also be observed when connecting this 

port. 

NI

ONI

RLY

24V 

DC

Содержание ZS5601

Страница 1: ...ment in PA installations With its gradual improvements over the years in terms of features construction and parts it is no doubt being the most wanted tool for PA setup Although it is not difficult to...

Страница 2: ...ing this switch regardless of any inactive zone Switching for zone 1 to 6 switching for zone 7 12 for ZS5121 only 2 3 4 ZS 5121 5 6 7 8 9 10 5 DC SUPPLY INPUT PORT 24V DC supply is required to operate...

Страница 3: ...IFIER ZONE OUTPUT CONNECTORS ZONE 1 TO 6 Output from amplifiers are connected to these terminals and speaker zoning is configured to the respective unit of ampli fier The user has the flexibility to c...

Страница 4: ...ier unit 1 is to serve zone 1 and 2 Power amplifier unit 2 is to serve zone 3 1 2 3 4 The diagram above shows installation of a 3 zone system with remote triggering employing external switches this is...

Страница 5: ...PIN 5 Z11 PIN 4 Z10 PIN 3 Z9 PIN 2 Z8 PIN 1 Z7 PIN 8 COM PIN 7 24V PIN 6 Z6 PIN 5 Z5 PIN 4 Z4 PIN 3 Z3 PIN 2 Z2 PIN 1 Z1 PIN 8 COM PIN 7 24V PIN 6 Z12 PIN 5 Z11 PIN 4 Z10 PIN 3 Z9 PIN 2 Z8 PIN 1 Z7 P...

Страница 6: ...ZS PIN 8 COM PIN 7 24V PIN 6 Z6 PIN 5 Z5 PIN 4 Z4 PIN 3 Z3 PIN 2 Z2 PIN 1 Z1 DC 24V CON RLY TRIG RLY PR ZS Connecting Emergency Overriding Port PAGE 6 ZS5601 ZS5121 ZONE SELECTOR to trigger volume con...

Страница 7: ...ated 482 x 44 x 180 mm 1 7 kg 6 8W 0 28A w All Call Cascade limitation 6 12 6 Individual zone switch Priority 2 1 kg RJ45 CONNECTOR TO REMOTE PAGING MIC NOTE ON UPGRADE VERSION Connection to remote pa...

Страница 8: ...the purchaser or the dealer for the period out of use of the unit moreover the warranty does not cover any damages which may be caused to people and things when using the product This warranty certif...

Отзывы: