4.1.22 iMac_RTD_Temp_ModDT
This UDT stores the iMAC RTD Temperature Input Module data. It can be used for RTD1 and RTD3
modules. It has the following members.
4.1.23 iMac_RTD3_FLAGS_ModDT
This UDT stores the iMAC RTD3 Flags Module data. It has the following members.
Member Name
Data Type
Description
RTD_Temp_Input
INT
Module Temperature Input
RTD_Temp_Status iMac_STATUS_DT Module Status
RTD_Temp_Resist INT
Module Resistance Value
RTD_Temp_Errors iMac_ERROR_DT
Module Error Counters
Member Name
Data Type
Description
RTD3_FLAGS_Bit0_T1_ALM
BOOL
Module Flags - RTD3 Temp1 Alarm Setpoint
RTD3_FLAGS_Bit1_T2_ALM
BOOL
Module Flags - RTD3 Temp2 Alarm Setpoint
RTD3_FLAGS_Bit2_T3_ALM
BOOL
Module Flags - RTD3 Temp3 Alarm Setpoint
RTD3_FLAGS_Bit3_ADC_Fail
BOOL
Module Flags - RTD3 Internal Fault (ADC Fail)
RTD3_FLAGS_Bit4_T1_Temp_OOR BOOL
Module Flags - RTD3 Temp1 Temperature Out
of Range
RTD3_FLAGS_Bit5_T2_Temp_OOR BOOL
Module Flags - RTD3 Temp2 Temperature Out
of Range
RTD3_FLAGS_Bit6_T3_Temp_OOR BOOL
Module Flags - RTD3 Temp3 Temperature Out
of Range
RTD3_FLAGS_Bit7_Calib_Error
BOOL
Module Flags - RTD3 Calibration Error
RTD3_FLAGS_Bit8_T1_OL_Status
BOOL
Module Flags - RTD3 Temp1 Online Status
RTD3_FLAGS_Bit9_T2_OL_Status
BOOL
Module Flags - RTD3 Temp2 Online Status
RTD3_FLAGS_Bit10_T3_OL_Status BOOL
Module Flags - RTD3 Temp3 Online Status
RTD3_FLAGS_Bit12_T1_Wire_FLT
BOOL
Module Flags - RTD3 Temp1 Sense Wire Fault
RTD3_FLAGS_Bit13_T2_Wire_FLT
BOOL
Module Flags - RTD3 Temp3 Sense Wire Fault