ABCM CHARGER USER MANUAL
11/03/2020 9:25
Page 16 of 19
Ampcontrol Electronics Pty Ltd
– ABN 35 000 770 141
ABCM Battery Charger User Manual
MAG-212, Rev 5
– March/2020
6.3.2 Battery
The following parameters specify the batteries to be installed in the ABCM Battery Charger:
Battery Type -
The ABCM Battery Charger is intended for Lead Acid type batteries.
Nominal Voltage -
This parameter is factory set and represents the type of charger (12V, 24V, 32V,
36V, 48V, 108V and 120V).
Rated Current -
This parameter is factory set and is determined by the size of the charger.
Battery Charging Current Limit -
The maximum charging current is factory set in consultation with
the customer.
The battery supply voltage and load current are displayed and monitored on the display.
6.4 Alarms
The alarms listed in this section are included as part of the standard supply. Other alarms may
have been included at the customer’s request. Please check purchase order to confirm.
6.4.1 Fault Notification
The ABCM Battery Charger allows for monitoring of a number of system parameters. Major and Minor
alarm levels can be configured for these system parameters, and some examples of these parameters
are listed below. All average and peak levels on analogue values are automatically logged in the Event
Log. Major and Minor alarms will energise when healthy. Temperature alarm and EL alarm will energise
when unhealthy. All outputs can be set to normally open (NO) or normally closed (NC).
All alarms can be accessed on the high resolution display of the controller - on the Status Mode screen
or through the Event Log. All alarms can be configured via the high resolution display, or remotely via an
Ethernet connection.
Major Alarm
Mains Fail
Earth Fault
Overvoltage
Undervoltage
No Battery
Overvoltage Relay
Undervoltage Relay
Low Voltage Warning
Minor Alarm
Overvoltage
Undervoltage
Earth Fault
6.4.2 Alarm Output Relays
The standard ABCM Battery Charger supply includes four output relays which allow for control of alarm
functions. These outputs allow control of minor and major faults, earth fault and undervoltage functions.
Additional relays can be provided to increase functionality. Contact Ampcontrol to confirm specific
requirements.