Appendix A.
DETECTOR CIRCUIT LIMITATIONS.
Detector Type
Quiescent Current
Circuit Limit
Thermal Detector
(opening on alarm)
0mA
No limit
Manual Call Point
0mA
No limit
Apollo Series 60 Heat Detector
(55000-105)
57mA
28
Apollo Series 60 Heat Detector
(55000-106)
57mA
28
Apollo Series 60 Heat Detector
(55000-107)
57mA
28
Apollo Series 60 Heat Detector
(55000-108)
57mA
28
Apollo Series 60 Ionisation Smoke
Detector (55000-200)
45mA
35
Apollo Series 60 Photoelectric
Smoke Detector (55000-300)
45mA
35 *
*This detector should be used with Gating switched off to meet the requirements of NZS 4512. See
operators manual section 5 for details.