AMPAC INDUSTRIES LTD
NZ 100 OPERATORS MANUAL
Page 14
Doc No: g0097wo1.doc
Dir No: L:\manuals
Date: 10/5/00
Rev: 1
Appendix A. DETECTOR CIRCUIT LIMITATIONS.
Detector Type
Quiescent Current
Circuit Limit
Thermal Detector
(opening on alarm)
0mA
No limit
Manual Call Point
0mA
No limit
Apollo Series 60 Heat Detector
(55000-105)
57mA
28
Apollo Series 60 Heat Detector
(55000-106)
57mA
28
Apollo Series 60 Heat Detector
(55000-107)
57mA
28
Apollo Series 60 Heat Detector
(55000-108)
57mA
28
Apollo Series 60 Ionisation Smoke
Detector (55000-200)
45mA
35
Apollo Series 60 Photoelectric
Smoke Detector (55000-300)
45mA
35 *
Hochiki America SIH 24F Ionization
Smoke Detector
40mA
40
Hochiki America SLK 24F
Photoelectric Smoke Detector
45mA
35
Fenwal CDP7051
Ionization Smoke Detector
45mA
35
Fenwal CDP7155
Photoelectric Smoke Detector
55mA
29 *
Photain Controls PRRP91
Heat Detector
65mA
24
Photain Controls ISD-P91
Ionisation Smoke Detectors
40mA
40
*This detector should be used with Gating switched off to meet the requirements of NZS 4512. See
operators manual section 5 for details.