AMPAC INDUSTRIES LTD
NZ 100 OPERATORS MANUAL
Page 12
Doc No: g0097wo1.doc
Dir No: L:\manuals
Date: 10/5/00
Rev: 1
7.0
SYSTEM OPERATION
7.1 RESETTING THE SYSTEM
To reset the system after a fire, press the ‘RESET’ button on the API665. This will return the
system back to its normal state. The buzzer will sound for confirmation.
7.2 USING THE WALK TEST FACILITY.
To start the walk test facility, press the ‘Walk Test’ switch on the API665. The buzzer will beep
once and the LED above the switch will illuminate.
The detectors can now be tested. As a detector is set into alarm the system will operate as
normal, except that after approximately four seconds the detectors on the circuit in alarm will be
reset. After testing is complete, press the ‘Walk Test’ switch to return to normal.
The walk test facility has an internal time out and will be de-selected automatically after ten (10)
minutes of operation.
7.3 TRIAL EVACUATION.
On the door of the NZ100 a key switch is provided for Trial Evacuation, operating this key switch
will cause the system to operate the bells. This will override any other bell isolate or silence
condition.