background image

En-4

7.  TURNING ON THE POWER

 CAUTION

•  Recheck the wiring. Incorrect wiring will cause trouble.

(1)  Check the remote controller wiring and DIP switch settings.
(2)  Check the indoor and outdoor unit wiring and circuit board switch 

settings, and then turn on the indoor and outdoor units.

(3)  If the power source is connected correctly, the 

 mark will be displayed 

in the center of the remote controller display.

 After 

” has fl ashed on the set temperature display for several 

second, the 

 mark will be displayed in the center of the remote 

controller display.

For the wiring and circuit board switch settings method, refer to the 
installation manual for the indoor unit and outdoor unit.

8. FUNCTION SETTING

This procedure changes the function settings used to control the indoor unit 
according to the installation conditions.
Incorrect settings can cause the indoor unit to malfunction.
Perform the “FUNCTION SETTING” according to the installation conditions 
using the remote controller.
•  Refer to the indoor unit installation manual for details on the function 

numbers and setting numbers.

•  Prepare for setting of indoor unit referring to installation manual of indoor 

unit before start of functional setting.

Start of Function setting mode

(1)  Press the “

” button, “

” button and “

” button for more than 

5 seconds simultaneously. Then shift to Function setting mode.

Function setting mode initial display

(2)  Press the “

” button or “

” button and select the Indoor unit 

number. Then press the “

” button.

Indoor unit number

Ex.  When Indoor unit number “00” is 

selected.

Function number and setting number setting

(3)  “Function number” display blinks. Then display Number by pressing the 

” button or “

” button.

Function number

(4)  When the “Setting number” blinks by pressing the “

” button set the 

Setting number by pressing the “

” button or “

” button.

Setting number 

Ex.  When Setting number “12” is 

selected.

(5)  Fix the setting by pressing the “

 ” button.

 

(Data is transferred to the indoor unit).

When set properly in the indoor unit.

    NO GOOD

 

(-- is displayed,) if not set the 
indoor unit.

 

Set again as per procedures 3-5 
above.

  GOOD

Completion of address setting mode

(6)  Function setting mode is released and returns to normal display if the 

” button, “

” button and “

” button are pressed for more than 

5 seconds simultaneously.

Normal mode display

 

*  Function setting mode is released automatically if no key is pressed 

for 60 seconds even the above buttons are not pressed.
(Switch to Function setting mode as per procedure 1 above. It is 
automatically released when Function setting)

(7)  After completing the FUNCTION SETTING, be sure to  turn off the 

power and turn it on again.

Note: 

•  Function Setting is available for Master remote controller only.

9371068114-04 EN.indd   Sec1:4

9371068114-04 EN.indd   Sec1:4

6/27/2557 BE   10:55 AM

6/27/2557 BE   10:55 AM

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Содержание UTY-RSNYM

Страница 1: ...gréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала MONTAJ KILAVUZU Yetkili servis personeli içindir 安装説明書 ࡩ ᜌ و ਜ਼ʡࢷĄ 9371068114 04 EN indd 1 93710...

Страница 2: ...mproperly performed might possibly result in personal harm to the user or damage to property Do not wire the remote controller cable and the bus wire together with or parallel to the connection cables transmission cables and power supply cables of the indoor and outdoor units It may cause erroneous operation When installing the bus wire near a source of electromagnetic waves use shield wire Do not...

Страница 3: ...the remote controller cable cord to the wall mounted type indoor unit do not connect it to the outdoor unit or the indoor unit power terminal block It may cause a failure There are 2 methods to connect the remote controller cable to the indoor unit One is the connection using contained connecting cable and the other is the connection the remote controller cable is connected to the exclusive termin...

Страница 4: ...remote controllers Master unit Slave unit DIP Switch 1 No 2 DIP Switch 1 No 2 1 Normal OFF 2 Dual OFF ON For the details refer to the installation manual of the indoor unit to be used 5 3 1 When connecting to the connector Connect the remote controller cable to the connecting cable and insert it to the connector Pattern 1 PCB Connecting cable cord Remote controller cable cord Connector Indoor unit...

Страница 5: ...n shift to Function setting mode Function setting mode initial display 2 Press the button or button and select the Indoor unit number Then press the button Indoor unit number Ex When Indoor unit number 00 is selected Function number and setting number setting 3 Function number display blinks Then display Number by pressing the button or button Function number 4 When the Setting number blinks by pr...

Страница 6: ... Description OPERATION lamp green TIMER lamp orange ECONOMY lamp green 1 1 Serial communication error 1 2 Wired remote controller communication error 1 5 Check run unfinished Setting error of Master unit or Slave unit or Remote controller 2 1 Unit number or Refrigerant circuit address setting error Simultaneous Multi 2 2 Indoor unit capacity error 2 3 Combination error 2 4 Connection unit number e...

Страница 7: ...1 Discharge temp error 10 3 Compressor temp error 10 4 High pressure error 10 5 Low pressure error 13 2 Branch boxes error Flexible Multi Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing If there is a problem with the air conditioner will be displayed Error code Faulty unit No 0 15 C0 If is displayed immediately contact authorized service personnel Do not used the operation below ...

Отзывы: