En-5

9. TEST OPERATION

(1)  If the operation lamp is on, press the “

 ” button to turn it off.

(2)  Press the “

” button and the “

” button at the same time for 

more than 2 seconds to start the test operation.

 

The operation lamp will light up and “

 ” will be displayed on the set 

temperature display.

(3)  To stop the test operation, press the “

” button.

* The 

” button or “

” button do not function. However, the other 

buttons can be used to change the settings.

Test operation is used for constrained operation of the outdoor unit.

Note:

• When “

” is indicated on temperature display, it means under 

maintenance. 
Indoor unit cannot be operated.

10. FILTER LAMP RESET

Some indoor unit models are equipped with a fi lter lamp in the indoor unit 
display to indicate when it is time to clean the air fi lters.

Press the “

” button for 2 seconds or more. The indoor unit fi lter lamp will 

go off and the fi lter display will disappear.

11. ERROR CODE

If you use a wired remote controller, error codes will appear on the remote 
controller display.
If you use a wireless remote controller, the lamp on the IR receiver unit 
will output error codes by way of blinking patterns. See the lamp blinking 
patterns and error codes in the table below. An error display is displayed 
only during operation.

Error display

Wired

remote

controller

Error code

Description

OPERATION

lamp

(green)

TIMER

lamp

(orange)

ECONOMY

lamp

(green)

(1)

(1)

Serial communication 
error

(1)

(2)

Wired remote controller 
communication error

(1)

(5)

• Check run unfi nished
• Setting error of Master 

unit or Slave unit or 
Remote controller

(2)

(1)

Unit number or 
Refrigerant circuit address 
setting error
[Simultaneous Multi]

(2)

(2)

Indoor unit capacity error

(2)

(3)

Combination error

(2)

(4)

• Connection unit number 

error (indoor slave unit) 
[Simultaneous Multi]

• Connection unit number 

error (indoor unit or 
branch unit) [Flexible 
Multi]

(2)

(7)

Master unit, slave unit 
set-up error [Simultaneous 
Multi]

(3)

(2)

Indoor unit PCB model
information error

(3)

(5)

Manual auto switch error

(4)

(1)

Inlet air temp. sensor 
error

(4)

(2)

Indoor unit Heat Ex. 
Middle temp. sensor error

(5)

(1)

Indoor unit fan motor error

(5)

(3)

Drain pump error

(5)

(7)

Damper error

(5)

(15)

Indoor unit error

(6)

(2)

Outdoor unit main PCB 
model information error or 
communication error

(6)

(3)

Inverter error

(6)

(4)

Active fi lter error, PFC 
circuit error

(6)

(5)

Trip terminal L error

(6)

(10)

Display PCB 
microcomputers
communication error

(7)

(1)

Discharge temp. sensor 
error

(7)

(2)

Compressor temp. sensor 
error

(7)

(3)

Outdoor unit Heat Ex. 
liquid temp. sensor error

(7)

(4)

Outdoor temp. sensor 
error

(7)

(5)

Suction Gas temp. sensor 
error

(7)

(6)

• 2-way valve temp. 

sensor error

• 3-way valve temp. 

sensor error

(7)

(7)

Heat sink temp. sensor 
error

9371068114-04 EN.indd   Sec1:5

9371068114-04 EN.indd   Sec1:5

6/27/2557 BE   10:55 AM

6/27/2557 BE   10:55 AM

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Содержание UTY-RSNYM

Страница 1: ...gréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала MONTAJ KILAVUZU Yetkili servis personeli içindir 安装説明書 ࡩ ᜌ و ਜ਼ʡࢷĄ 9371068114 04 EN indd 1 93710...

Страница 2: ...mproperly performed might possibly result in personal harm to the user or damage to property Do not wire the remote controller cable and the bus wire together with or parallel to the connection cables transmission cables and power supply cables of the indoor and outdoor units It may cause erroneous operation When installing the bus wire near a source of electromagnetic waves use shield wire Do not...

Страница 3: ...the remote controller cable cord to the wall mounted type indoor unit do not connect it to the outdoor unit or the indoor unit power terminal block It may cause a failure There are 2 methods to connect the remote controller cable to the indoor unit One is the connection using contained connecting cable and the other is the connection the remote controller cable is connected to the exclusive termin...

Страница 4: ...remote controllers Master unit Slave unit DIP Switch 1 No 2 DIP Switch 1 No 2 1 Normal OFF 2 Dual OFF ON For the details refer to the installation manual of the indoor unit to be used 5 3 1 When connecting to the connector Connect the remote controller cable to the connecting cable and insert it to the connector Pattern 1 PCB Connecting cable cord Remote controller cable cord Connector Indoor unit...

Страница 5: ...n shift to Function setting mode Function setting mode initial display 2 Press the button or button and select the Indoor unit number Then press the button Indoor unit number Ex When Indoor unit number 00 is selected Function number and setting number setting 3 Function number display blinks Then display Number by pressing the button or button Function number 4 When the Setting number blinks by pr...

Страница 6: ... Description OPERATION lamp green TIMER lamp orange ECONOMY lamp green 1 1 Serial communication error 1 2 Wired remote controller communication error 1 5 Check run unfinished Setting error of Master unit or Slave unit or Remote controller 2 1 Unit number or Refrigerant circuit address setting error Simultaneous Multi 2 2 Indoor unit capacity error 2 3 Combination error 2 4 Connection unit number e...

Страница 7: ...1 Discharge temp error 10 3 Compressor temp error 10 4 High pressure error 10 5 Low pressure error 13 2 Branch boxes error Flexible Multi Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing If there is a problem with the air conditioner will be displayed Error code Faulty unit No 0 15 C0 If is displayed immediately contact authorized service personnel Do not used the operation below ...

Отзывы: