Industry Cellular Gateway
Modbus Proxy Rule Configuration
Item
Value setting
Description
Name
A Must filled setting.
Specify a name as the identifier of the Modbus proxy rule.
Value Range
:
1 ~ 32 characters.
Modbus Slave Type IP Address :Port
is
selected by default.
Specify the Modbus Slave devices to apply with the Modbus proxy rule. It can be
IP Address:Port
for Modbus TCP slaves or
Local Serial Port
for local attached
Modbus RTU/ASCII slaves.
Value Range
:
1 ~ 65535 for port number
Slave ID
1. A Must filled setting.
2. Range 1 to 247
Specify the ID range for the slave device(s) to apply with the Modbus proxy rule.
Value Range
:
1 ~ 247.
Function Code
Read Coils (0x01)
is
seelected by default.
Specify a certain read function for the Data Logging Proxy to issue and record the
responses from device(s).
Start Address
1. A Must filled setting.
2. Range 0 to 65535
Specify the Start Address of registers to apply with the specified function code.
Value Range
:
0 ~ 65535.
Number of
Coils/Registers
1. A Must filled setting.
2. Range 1 to 125
Specify the number of coils/registers to apply with the specified function code.
Value Range
:
1 ~ 125.
Note:
Start Address
plus
Number
must be smaller than 65536.
Polling Rate (ms)
1. A Must filled setting.
2.
1000
ms is set by
default
Enter the poll time in milliseconds to apply the Proxy Mode Rule.
Once the proxy mode is activated, the Modbus Gateway will issue pre-defined
Modbus message on each Poll Time interval accordingly.
Value Range
:
500 ~ 99999.
Save
N/A
Click the
Save
button to save the settings.
Undo
N/A
Click the
Undo
button to cancel the changes.