![Amit IOG761 Скачать руководство пользователя страница 208](http://html.mh-extra.com/html/amit/iog761/iog761_user-manual_2933376208.webp)
Industry Cellular Gateway
4.2.1 Data Logging Configuration
D
ata Logging is commonly used in monitoring systems to collect and analyze the field data. With proper
configuration, the Gateway will record Modbus messages according to the specified rule list.
Go to
Field Communication > Data Logging > Configuration
tab.
Enable Data Logging
Configuration
Item
Value setting
Description
Data Logging
The box is unchecked
by default.
Check the
Enable
box to activate to data logging function.
Storage Device
External
is set by
default
Choose the sotrage device to store the log files. It can be
External
or
Internal
,
depends on the product specification.
Save
NA
Click the
Save
button to save the settings.
Note:
1. If there is no available storage device, the Enable checkbox will be grayed, and you can’t enable it for the
data logging. That is, if you selected External Storage, plug-in the storage first, and then enable the function
and also make the required configuration.
2. Make sure the Modbus Operation Mode is selected and enabled, or there will be no Modbus transactions
to be logged. Please refer to
Field Communication > Bus & Protocol > Port Configuration
and
Modbus
tabs.
Create/Edit Modbus Proxy Rules
The Gateway allows you to customize your proxy mode rule list. It supports up to a maximum of 20 rules.
When the
Add
button is applied,
Modbus Proxy Rule Configuration
screen will appear.