AMF² 36K + HMI 08.2013
Page 54 of 71
4. Start-up and First Operation (
See page 16-17 for detailed drawings)
In order to achieve maximum performance and smooth operation of the filter it is crucial to perform the Startup and First
Operation procedures exactly as described in this section. Please read carefully the following instructions prior to any
attempt to operate the filter.
Commissioning the filter should be done by an authorized Amiad technician, do not attempt to commission
the filter unaccompanied.
Please contact your supplier for coordinating a technician visit.
Failing to coordinate the start-up process with your supplier may lead to undesired damage and may affect
your warranty coverage.
The start-up procedure is a multistage process; the following checklists describe step by step the actions to be done in
order to successfully commission the filter:
4.1
Dry stage – connections verification
Important notes:
Before starting the dry stage of the filter start-up it is very important to make sure that the filter is empty and isolated
from the water system by verifying visually that:
The upstream and the downstream manual isolation valves are closed
The flushing water supply line isolation valve is manually closed
Consult your Certified Installation Arrangement Drawings for these manual valves details.
The following checklist lists the actions and the tasks order to be done during the dry stage.
√ Num. Action
Picture
4.1.1
Main piston positioning:
In order to ensure that the main piston’s spry nozzles are
not within the cassette package limits, it is necessary to
verify that the main piston is at SW1 switch position.
1.
Remove the plug from the piston inlet
located at the left side of the cartridge
cover
.
2.
Insert a clean and straight 4.5 meter 0.5” pipe or
rod through the opened connection (
The Tune-up
Rod as described at section 2.1.6.)
.
3.
Using the rod push the piston all the way in and
then remove the rod out of the filter.
1
2
Содержание AMF-36K
Страница 16: ...Figure 25 ...
Страница 17: ...AMF 36K HMI 08 2013 Page 17 of 71 ...
Страница 23: ...AMF 36K HMI 08 2013 Page 23 of 71 1 3 ...
Страница 36: ...AMF 36K HMI 08 2013 Page 36 of 71 Press this To get this Press this To get this Press this To get this ...
Страница 65: ...AMF 36K HMI 08 2013 Page 65 of 71 5 3 Control cabinet drawings ...
Страница 66: ...AMF 36K HMI 08 2013 Page 66 of 71 ...
Страница 67: ...AMF 36K HMI 08 2013 Page 67 of 71 ...
Страница 68: ...AMF 36K HMI 08 2013 Page 68 of 71 ...
Страница 69: ...AMF 36K HMI 08 2013 Page 69 of 71 ...
Страница 70: ...AMF 36K HMI 08 2013 Page 70 of 71 ...