This screen allows the operator to set:
Type of Analog Input A.
– The PLC has 2 analog inputs A & B. This
parameter set the task of Analog Input A. It can be a DP meter or
Outlet pressure meter.
Max. Range of DP Analog Input –
If Analog Input A. is set as a DP
then this parameter sets the maximum range of the DP Meter.
Note:
Since the meter is of 4-20 type, the software assumes that
DP of
ø
bar is equal to 4 milliamps. So the user has to enter only
the maximum DP value for the 20 milliamp reading. Default
values are 1 bar or 15 PSI.
Max. Range of Analog In/Out Press
– If Analog Input A. is set as a
DP then Analog Input B. is used as Inlet Pressure meter. This
parameter sets the maximum range of the Inlet Pressure Meter.
However if Analog meter A. is not set as a DP meter then Analog
Input A. is set as Outlet Pressure and Analog Input B. is set as
Inlet pressure.
If the user would like to flush the filter according to a differential
Pressure it is necessary to install two pressure meters; Inlet and
Outlet. In such case this parameter is used to set the maximum
range of the Inlet and the Outlet Pressure Meters. The DP
reading in this case is calculated by the software by subtracting
the outlet pressure from the inlet pressure.
Note:
Since the meters are of 4-20 type, the software assumes
that Pressure of
ø
bar is equal to 4 milliamps. So the user has to
enter only the maximum Pressure value for the 20 milliamp
reading, i.e. 10 bar, 16 bar, etc.
Note:
in case of 2 pressure meters they must be of the same type
and the same range.
Maximum Idle / Pause Time
– Set the maximum time for Idle or
Pause. This parameter is useful when the filter is filling a tank
with the filtered water. When the tank is full the filter enters to
pause-mode. In order to ensure that the filter remains clean the
user may set a time in this field. In such case if the pause is
prolonged, the filter will enter to a flushing cycle once the time
entered at this filed is exceeded. Enter 9999 for disabling this
option.
Содержание AMF-36K
Страница 16: ...Figure 25 ...
Страница 17: ...AMF 36K HMI 08 2013 Page 17 of 71 ...
Страница 23: ...AMF 36K HMI 08 2013 Page 23 of 71 1 3 ...
Страница 36: ...AMF 36K HMI 08 2013 Page 36 of 71 Press this To get this Press this To get this Press this To get this ...
Страница 65: ...AMF 36K HMI 08 2013 Page 65 of 71 5 3 Control cabinet drawings ...
Страница 66: ...AMF 36K HMI 08 2013 Page 66 of 71 ...
Страница 67: ...AMF 36K HMI 08 2013 Page 67 of 71 ...
Страница 68: ...AMF 36K HMI 08 2013 Page 68 of 71 ...
Страница 69: ...AMF 36K HMI 08 2013 Page 69 of 71 ...
Страница 70: ...AMF 36K HMI 08 2013 Page 70 of 71 ...