20

MAINTENANCE OF YOUR WATER HEATER

Draining and Flushing

It is recommended that the tank be drained and flushed 
every 6 months to remove sediment which may build up 
during operation. The water heater should be drained if 
being shut down during freezing temperatures. To drain the 
tank, perform the following steps:

1.  Turn off the gas to the water heater at the manual gas 

shut-off valve.

2.  Close the cold water inlet valve.

3.  Open a nearby hot water faucet.

4.  Connect a hose to the drain valve and terminate it to an 

adequate drain.

Note:

  The drain hose should be rated for at least 200°F. 

If the drain hose does not have this rating, open the cold 
water inlet valve and a nearby hot faucet until the water is 
no longer hot.

5.  Open the water heater drain valve and allow all the 

water to drain from the tank. Flush the tank with water 
as needed to remove sediment.

6.  Close the drain valve, refill the tank, and restart the 

heater as directed under “Operating Your Water 
Heater”.

If the water heater is going to be shut down for an extended 
period, the drain valve should be left open.

Important:

  Condensation may occur when refilling the 

tank and should not be confused with a tank leak.

Routine Preventative 
Maintenance

At least annually, a visual inspection should be made of 
the venting and air supply system, piping systems, main 
burner, pilot burner, and flame-trap. Check the water heater 
for the following:

• 

Obstructions, damage, or deterioration in the venting 
system. Make sure the ventilation and combustion air 
supplies are not obstructed. 

• 

Build up of soot and carbon on the main burner and 
pilot burner. Check for a soft blue flame.

• 

Leaking or damaged water and gas piping.

• 

Presence of flammable or corrosive materials in the 
installation area.

• 

Presence of combustible materials near the water 
heater.

• 

Verify proper operation after servicing this water heater.

Important:

  If you lack the necessary skills required to 

properly perform this visual inspection, you should not 
proceed, but get help from a qualified service technician.

Temperature and Pressure 
Relief Valve

Explosion Hazard

If the temperature and pressure relief
valve is dripping or leaking, have a
qualified service technician replace it.

Do not plug valve.
Do not remove valve.

Failure to follow these instructions can
result in death or explosion.

Manually operate the temperature and pressure relief valve 
at least once a year to make sure it is working properly. 
To prevent water damage, 
the valve must be properly 
connected to a discharge 
line which terminates 
at an adequate drain. 
Standing clear of the outlet 
(discharged water may be 
hot), slowly lift and release 
the lever handle on the 
temperature and pressure 
relief valve to allow the valve to operate freely and return to 
its closed position. If the valve fails to completely reset and 
continues to release water, immediately shut off the manual 
gas valve and the cold water inlet valve and call a qualified 
service technician.

Figure 21

Temperature and Pressure
Relief Valve

Manual Relief
Valve

Discharge line to drain

Содержание 6510381

Страница 1: ...med by a qualified installer service agency or the gas supplier WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal...

Страница 2: ...as been under water Immediately call a qualified service technician Water heaters subjected to flood conditions or anytime the gas controls main burner or pilot have been submerged in water require re...

Страница 3: ...y personnel a licensed plumber or an authorized service person Important This water heater has a resettable thermal switch installed as part of the Flame Guard Safety System DO NOT attempt to disable...

Страница 4: ...led or leaked in the area of the water heater leave the area immediately and call the fire department from a neighbor s home Do not attempt to clean the spill until all ignition sources have been exti...

Страница 5: ...stible materials are stated on the data plate adjacent to the gas control valve thermostat of the water heater The water heater is certified for installation on a combustible floor Important If instal...

Страница 6: ...f the water heater as shown The drip leg must be no less than three inches long for the accumulation of dirt foreign material and water droplets Figure 3 Gas Piping Manual Gas Shut off Valve Ground Jo...

Страница 7: ...areas Combustion air must be free of acid forming chemicals such as sulfur fluorine and chlorine These elements are found in aerosol sprays detergents bleaches cleaning solvents air fresheners paint a...

Страница 8: ...an be drawn from outside of the enclosure One opening shall be within 12 inches of the top and one within 12 inches of the bottom of the enclosure as shown in Figure 4 The size of each opening free ar...

Страница 9: ...supply openings consideration must be given to the blocking effect of protection louvers grilles and screens These devices can reduce airflow which in turn may require larger openings to achieve the...

Страница 10: ...n existing water heater be sure to use the new drafthood supplied with the water heater Figure 9 Drafthood Installation Sheet Metal Screws four provided Drafthood Jacket top Install the drafthood with...

Страница 11: ...erms of its listing It must be connected to the water heater s drafthood by a certified vent connector or by directly originating at the drafthood opening Vertical gas vents must terminate with a list...

Страница 12: ...ine as shown in Figure 14 These valves reduce the point of use temperature of the water by mixing cold and hot water and are readily available for use 4 If installing the water heater in a closed wate...

Страница 13: ...s DO NOT add any chemicals to the system piping which will contaminate the potable water supply Closed System Thermal Expansion Periodic discharge of the temperature and pressure relief valve may be d...

Страница 14: ...higher than the working pressure shown on the data plate of the water heater The Discharge Line Must not be smaller than the pipe size of the relief valve or have any reducing coupling installed in th...

Страница 15: ...the system Otherwise these bubbles will be trapped in the air handler heat exchanger coil reducing the efficiency Do not connect the water heater to any system or components previously used with non...

Страница 16: ...reduce the likelihood of a flammable vapor ignition incident New technology used in meeting these standards makes this product less tolerant of installation errors or improper installation environmen...

Страница 17: ...with the igniter repeat steps 4 7 Continue to hold the button for about 1 minute after the pilot is lit Release the reset button and it will pop back up Pilot should remain lit If the pilot light goe...

Страница 18: ...r Temperature Regulation UNITROL BEFORE LIG HTIN G READ ALL IN STRUCTIO NS CAUTIO N H O T W A R M V A C A T I O N CAUTION W A TER INCREAS E S HOTTER T H E RISK OF SCALD INJ U R Y V A C A T I O N WAR M...

Страница 19: ...rt on page 26 Reset the thermal switch by depressing the small button in the center of the thermal thermal switch Important Correct any issues prior to resetting the thermal switch DO NOT attempt to d...

Страница 20: ...age or deterioration in the venting system Make sure the ventilation and combustion air supplies are not obstructed Build up of soot and carbon on the main burner and pilot burner Check for a soft blu...

Страница 21: ...to see if it is dirty or clogged The burner may be cleaned with soap and hot water Figure 24 N O T W A H S T R E B O R I A C A V M R A W U T O H T H E R I SK OF Y R U J N I D L A C S R E T T O H W A...

Страница 22: ...ly Page 23 Figure 25 Two Piece Wire Connector Assembly Two Piece Wire Connector Thermocouple Retainer Clip Manifold Door Other fittings not shown for clarity Pilot T ube Igniter Wire Figure 26 Thermoc...

Страница 23: ...lve for leaks Test the supply connections by brushing on an approved noncorrosive leak detection solution Bubbles forming indicate a leak Correct any leak found 9 Follow the lighting instructions on p...

Страница 24: ...ant The gas control valve thermostat is a standard valve with wire leads that connect to a thermal switch Removing the Gas Valve 1 On the gas control valve thermostat turn the temperature dial counter...

Страница 25: ...te heater 7 Correct piping dip tube must be in cold inlet 8 Advise customer DRIP FROM RELIEF VALVE 1 Excessive water pressure 2 Heater stacking 3 Closed water system 1 Use a pressure reducing valve an...

Страница 26: ...nstructions section of this manual for specific requirements NO Is the pilot tube damaged NO Does the flame trap show signs of discoloration and or debris Shut off the gas supply to the water heater a...

Страница 27: ...y System parts Item No Parts Description 1 DRAFTHOOD 2 REDUCER RING SOME MODELS 3 FLUE BAFFLE 4 HEAT TRAP COLD SOME MODELS 5 HEAT TRAP HOT SOME MODELS 6 COLD WATER DIP TUBE 7 ANODE ROD 8 TEMPERATURE P...

Страница 28: ...e wire connector with retainer clip thermal switch and pilot assembly Natural Gas Low Nox Item 17 Manifold door assembly which contains the manifold tube gasket door pilot tube thermocouple two piece...

Отзывы: