Appendix

Maintenance

Code Blue

Operation

Contr

ol Station

Clock/Timer

12

Important Considerations

The ATSTCS 

must be 

in the RUN mode for Code Blue to override.

The 12vac/vdc to 30vac/vdc signal that starts the Code Blue timer originates from equipment external to the Digital Clock/
Timer. The external equipment usually employs a switch device (i.e., a relay contact) to apply this signal. That switching 
device is often referred to as the Code Blue contact.

The Code Blue contact does not have to open before resetting the clock/timer back to normal operation, but must be opened 
before another Code Blue can occur. The transition from no voltage to applied voltage (across the K2+ and K2- terminals) 
initiates a Code Blue.

If the Code Blue contact opens and closes again before the clock/timer is reset back to normal operation, the Code Blue timer 
will start over from 00:00:00.

If a power failure occurs during a Code Blue and the back up battery is in place, and the Code Blue contact is still closed 
when the power returns, the Code Blue timer will start over from 00:00:00. If the Code Blue contact is open when the power 
returns, the Code Blue timer will continue counting the elapsed time including the time while the power was off.

If a power failure occurs during a Code Blue after the Code Blue timer has been stopped for viewing, and the Code Blue 
contact is still closed when the power returns, the Code Blue timer will start over from 00:00:00. If the Code Blue contact 
is open when the power returns, the elapsed time where the Code Blue timer was stopped prior to the power failure will be 
displayed.

Содержание SiteSync IQ SQA261RSAES

Страница 1: ...Installation and Operation Manual Part H004242 Rev 4 October 2011 Wireless Digital Clock Elapsed Time Indicator with Code Blue...

Страница 2: ...tive Devices CAUTION This equipment contains electronic devices that are sensitive to static electric charges To guarantee protection for the circuitry of this unit it is required that electrostatic h...

Страница 3: ...et Time 10 Down Counter Elapsed Time Operation 10 Code Blue Description 11 11 Operations 11 Wiring 11 Important Considerations 12 Operating Maintenance 13 Cleaning 13 Battery Maintenance 13 System Mai...

Страница 4: ...set Both timer modes have a programmable preset value When the timer reaches the preset value a two second audible alarm sounds from a speaker in the control station The clock control station contains...

Страница 5: ...n gang box G hot neutral ground wires to non switched electrical circuit wiring using UL approved wire nuts Route field wiring away from sharp projections corners and internal components For Molex whi...

Страница 6: ...ing Appendix Maintenance Code Blue Operation Control Station Clock Timer K2 K2 K1 K1 12VAC 12VAC UNREG GND PIEZO S5 S4 S3 S2 S1 CHASSIS NEUTRAL 120VAC MASTER CLOCK TERMINAL BLOCK Typical wiring for th...

Страница 7: ...an SQA261RSAEA Master Clock connect the 3 Interconnecting Wires J from the SQA261RSAES Slave Clock using UL approved wire nuts z Mount back cover A to electrical box D using 2 screws single gang or 4...

Страница 8: ...er mode Clock Position This position is used to choose clock mode Down Position This position is used to choose down counting elapsed timer mode Start Stop Increment Switch This button is used to star...

Страница 9: ...field wires into the double gang box v Connect field wiring interconnecting the ATSTCS Control Station with the Digital Clock Timer to the appropriate wires of the Control Station See wiring detail b...

Страница 10: ...24 hour mode option is configured by the display settings of the system controller The ATSTCS control station will allow the user to set a 12 or 24 mode and time when the SET RUN switch is in the SET...

Страница 11: ...n v Set the SET RUN switch to the SET position The hours digits will be flashing w Using the INCREMENT switch set the desired hours for the preset time then press ENTER The minutes digits will now be...

Страница 12: ...d the time held for viewing by pressing the START STOP button on the ATSTCS switch panel The Code Blue timer cannot be restarted from the switch panel To reset the clock back to normal operation the R...

Страница 13: ...nals initiates a Code Blue If the Code Blue contact opens and closes again before the clock timer is reset back to normal operation the Code Blue timer will start over from 00 00 00 If a power failure...

Страница 14: ...be erased by deeply discharging the battery and recharging it It is recommended that the operator remove 120vac power from the Digital Clock Timer once per year for at least four hours nNote There is...

Страница 15: ...be changed and the alarm will not sound Appendix 2 Using the Digital Clock Timer as a Count Down Elapsed Timer Only For applications where the user does not want to use the clock and up count function...

Страница 16: ...to change Push ENTER Clock displays flashing minutes digits Push INCREMENT to change Push ENTER Clock displays flashing seconds digits Push INCREMENT to change Push ENTER Display shows DONE Place SET...

Отзывы: