113345-9
www.amdry.com
5
!
!
!
!
Unpacking/Setting Up _________________
Remove protective shipping material (i.e., plastic wrap, and/
or optional shipping box) from dryer.
Important
Dryer must be transported and handled in an upright
position at all times.
The dryer can be moved to its final location while still attached
to the skid or with the skid removed. To unskid the dryer,
locate and remove the four (4) bolts securing the base of the
dryer to the wooden skid. Two (2) are at the rear base (remove
the back panel for access), and two (2) are located in the
bottom of the lint chamber. To remove the two (2) bolts located
in the lint chamber area, remove the lint door.
With the skid removed, to make it easier to slide the dryer into
its final position, slightly lower all four (4) leveling legs, so
that the dryer will slide on the legs instead of the base frame.
The lint coops of all dryers are supported during shipping by
a bracket. Remove this bracket before starting the dryer.
Leveling Dryer
The dryer is equipped with four (4) leveling legs, one (1) at
each corner of the base. Two (2) are located at the rear of the
dryer base, and two (2) are located in the lint chamber (coop).
To increase bearing life and improve efficiency, the dryer
should be tilted slightly to the rear.
Bulkheads and partitions should be
made of noncombustible materials
and must be located a minimum of
12-inches (30.48 cm) (18-inches
[45.72 cm] or more is recommended
f o r e a s e o f i n s t a l l a t i o n ,
maintenance, and service) above
the dryer outer top, except along the
front of the dryer which may be
partially closed in if desired. The
clearance between the bulkhead
header and the dryer must be a
minimum of 4-inches (10.16 cm) and
must not extend more than 4-inches
(10.16 cm) to the rear of the front.
The bulkhead facing must not be
closed in all the way to the top of the
dryer. A 1-inch (2.54 cm) clearance
is required.
Note
Allowances must be made
for opening the control
door.
Dryers may be positioned sidewall
to sidewall. However, a 1/16” (1.58
mm) minimum allowance must be
made for the opening and closing of
the control door and the lint door. It
Important
When fire sprinkler systems are located above the
dryers, a minimum of 18-inches (45.72 cm) above
the dryer console (module) is required. Dryers may
be positioned sidewall to sidewall however, a 1/16” (1.58 mm)
minimum allowance is required between dryers (or wall) for
ease of installation and maintenance. Allowances must be
made for the opening and closing of the control door and the
lint door.
Dryer Enclosure Requirements________
is suggested that the dryer be positioned about 2 feet (0.61
meters) away from the nearest obstruction for ease of
installation, maintenance, and service (to be measured from
the back guard). Refer to the illustration above for details.
Note
Air considerations are important for proper and
efficient operation.
Содержание ML-55 Phase 7
Страница 26: ...ADC 113345 9 12 01 04 6 ...