To protect the outside end of the horizontal ductwork from the weather, a 90º elbow bent downward should
be installed where the exhaust exits the building. If the exhaust ductwork travels vertically up through the
roof, it should be protected from the weather by using a 180º turn to point the opening downward. In either
case, allow at least twice the diameter of the duct between the duct opening and nearest obstruction.