26
American Dryer Corporation
113549 - 8
210 NON-TILT (GAS – REAR EXHAUST)
7.5 hp Blower Motor / 3 hp Drive Motor
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT
:
NOTES
: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering,
specify exact voltage.
When fuses are used they must be dual element, time delay, current
limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse value,
by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type ONLY.
For others, calculate/verify correct breaker size according to appliance
amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz
50 Hz
208
3ø
3 / 4
36.2
—
60
220
3ø
3
35.2
—
60
230
3ø
3
—
35.1
60
240
3ø
3
34.2
—
60
380
3ø
3 / 4
—
20.2
30
400
3ø
3 / 4
—
20
30
416
3ø
3 / 4
—
19.9
30
440
3ø
3
19.1
—
30
460
3ø
3
18.1
—
30
480
3ø
3
18.1
—
30
575
3ø
3
14.9
—
20
2. Electrical Service Specifications
3/9/17
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is affixed
to the right electrical control panel.
WARNING: 208 VAC AND 240 VAC ARE NOT THE SAME. Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
NOTE: ADC reserves the right to make any changes in specifications at any time without notice or
obligation.
Содержание AD-210
Страница 15: ...113549 8 www adclaundry com 11 1 Reassembly Instructions For Gas Dryer Shipped In Two 2 Pieces ...
Страница 17: ...113549 8 www adclaundry com 13 2 Reassembly Instructions For Steam Dryer Shipped In Two 2 Pieces ...
Страница 23: ...113549 8 www adclaundry com 19 210 STEAM DRYER 6 500 CFM 184 CMM HORIZONTALDRYERVENTING ...
Страница 66: ...ADC Part No 113549 8 04 08 22 ...