C
OMMAND
M
ODE
D
ATA
F
ORMAT
SMD23E2 and SMD24E2 User Manual
ADVANCED MICRO CONTROLS INC.
74
Command Word 1 (continued)
Bit 5: Save_to_Flash -
This bit can be used to save a programmed Assembled Move to flash memory or to
store the absolute encoder position offset to flash. (The absolute encoder position offset is generated
by the Encoder Preset command.)
When using this bit to save the programmed Assembled Move to flash memory, this bit must be
set when the Program_Assembled bit (Command Word 0, bit 12) makes a 1
0 transition at the
end of the programming cycle. The unit responds by flashing the Status LED when the writing is
complete. If the LED is flashing green, the write to flash memory was successful. If it flashes
red, then there was an error in writing the data. In either case, power must be cycled to the unit
before you can continue. This design decision is to protect the flash memory from constant write
commands. The flash memory has a minimum of 10,000 write cycles.
When using this bit to save the calculated absolute encoder offset value to flash memory, this bit
must be set when the Preset Encoder command is issued. (Bit 14 of
is set to
“1”, see page 71.) If the offset is stored without error, the unit will respond by setting the
Acknowledge bit. (Bit 13 of
, see page page 86.)
Bit 4: Reverse_Blend_Direction –
When you command a Blend Move to run, this bit determines the direc-
tion of rotation. Set to “0” for a clockwise Blend Move, “1” for a counter-clockwise Blend Move.
Bits 3-2: Reserved –
Must equal “0”.
Bit 1: Motor Current –
If reset to “0” when a move command is issued, the motor current will be the value
specified when the SMD23E2 or SMD24E2 was configured. Set to “1” to program the motor current
to the value in word 8 of the command block. Motor current can set as a separate command or as part
of a move command.
Bit 0: Reserved –
Must equal “0”.
Command Blocks
The following section lists the output data format for the sixteen different commands.
Absolute Move
Table R6.2 Absolute Move Command Block
PROFINET
Word
Function
Units
Range
0
16#0001
1
See pg. 73
2
Abs. Target Position: Upper Word
Steps
Combined value between
–8,388,608 and +8,388,607
3
Abs. Target Position: Lower Word
4
Programmed Speed: Upper Word
Steps/Second
Combined value between
the Configured Starting
Speed and 2,999,999
5
Programmed Speed: Lower Word
6
Acceleration
Steps/sec/ms
1 to 5000
7
Deceleration
Steps/sec/ms
1 to 5000
8
Motor Current
0.1 amps
0 to 34. Ignored if bit 1 of
Command Word 1 is not set.
9
Acceleration Jerk
0 to 5000
Содержание SMD23E2 Series
Страница 10: ...ABOUT THIS MANUAL SMD23E2 and SMD24E2 User Manual ADVANCED MICRO CONTROLS INC 10 Notes...
Страница 44: ...MOTION CONTROL SMD23E2 and SMD24E2 User Manual ADVANCED MICRO CONTROLS INC 44 Notes...
Страница 54: ...CALCULATING MOVE PROFILES SMD23E2 and SMD24E2 User Manual ADVANCED MICRO CONTROLS INC 54 Notes...
Страница 68: ...CONFIGURATION MODE DATA FORMAT SMD23E2 and SMD24E2 User Manual ADVANCED MICRO CONTROLS INC 68 Notes...
Страница 88: ...COMMAND MODE DATA FORMAT SMD23E2 and SMD24E2 User Manual ADVANCED MICRO CONTROLS INC 88 Notes...
Страница 124: ...ETHERNET IP EXPLICIT MESSAGING SMD23E2 and SMD24E2 User Manual ADVANCED MICRO CONTROLS INC 124 Notes...
Страница 128: ...MODBUS TCP CONFIGURATION SMD23E2 and SMD24E2 User Manual ADVANCED MICRO CONTROLS INC 128 Notes...
Страница 134: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...