I
NSTALLING
THE
NX2A4E2
NX2A4E2 User Manual
ADVANCED MICRO CONTROLS INC.
42
1.10 DC Input Wiring
Input 1 can be used to monitor the stopping time of resolver 1 if the NX2A4E2 has channel 1 configured for a
single resolver transducer. This input is labeled “BRAKE” on the front of the unit. Input 2 is presently not
implemented on the NX2A4E2.
Input 1 is a differential input that can be wired to accept sourcing or sinking sensors. It accepts 10 to 30 Vdc
without the need for an external current limiting resistor. Figure T1.12 below shows how to wire discrete DC
sourcing and sinking sensors to input 1 of the NX2A4E2.
Figure T1.12 Input Wiring
1.10.1 Cable Shields
Because they are low power signals, cabling from the sensor to the NX2A4E2 should be done using a twisted
pair cable with an overall shield. The shield should be grounded at the end when the signal is generated,
which is the sensor end. If this is not practical, the shield should be grounded to the same ground bus as the
NX2A4E2.
NX2A4E2 Connection to Sourcing Sensor Output
NX2A4E2 Connection to Sinking Sensor Output
OUT
OUT
OUT
–
–
1 2
1 2
Содержание NEXUS NX2A4E2
Страница 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0N090 E2 Technology...
Страница 16: ...NX2A4E2 INTRODUCTION NX2A4E2 User Manual ADVANCED MICRO CONTROLS INC 16 Notes...
Страница 28: ...DATA FORMATS NX2A4E2 User Manual ADVANCED MICRO CONTROLS INC 28 Notes...
Страница 52: ...PROTOCOL SPECIFIC INFORMATION NX2A4E2 User Manual ADVANCED MICRO CONTROLS INC 52 Notes...
Страница 56: ...INSTALLING AN EDS FILE EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 56 Notes...
Страница 66: ...ETHERNET IP EXPLICIT MESSAGING EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 66 Notes...
Страница 70: ...MODBUS TCP CONFIGURATION Modbus TCP Protocol ADVANCED MICRO CONTROLS INC 70 Notes...
Страница 76: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...