Always
O
n UPS Systems
M0703_NX_Series_Operators_Manual
V1.25
2012-06-12 32
D: Buzzer outlet:
There is a buzzer located behind the LCD Display. The buzzer will allow for
audile notification during an abnormal condition. The buzzer will be activated
under one of the following conditions: (The frequency of the buzzer is also
described for your reference.)
•
INVERTER IS OVERLOADED
>110%, beep once / 3 seconds
>125%, beep once / second
>150%, beep twice / second
•
BACK-UP
>320VDC, beep once/ 3
seconds
<320VDC, beep twice / second
<295VDC, no beeping
•
INVERTER IS SHORT CIRCUITED
beep continuously
•
FUSE BROKEN
beep continuously
•
HEAT SINK OVER TEMPERATURE
beep
continuously
•
HIGH DC SHUTDOWN
beep continuously
•
BYPASS ON STOP
beep continuously
•
EMERGENCY STOP
beep
continuously
The buzzer will beep once every time the inverter is switched on or off. This
will allow for the user to be sure the operation was preformed correctly.
E. Bypass LED:
This LED is lit when the maintenance bypass breaker is closed leaving the
inverter in the off mode. If the inverter is active when the bypass breaker is
closed the inverter will shutdown immediately.
F. Reserve LED:
This LED is lit when the reserve breaker is closed, and the supply is within
operating parameters.
G. Rectifier LED:
This LED is lit when the rectifier is operating, the supply is within operating
parameters, the rectifier breaker is closed and the DC bus voltage is within
operating parameters.
H. Battery LED:
This LED is lit while the UPS is in back-up mode. This LED also indicates the
results of battery test. If the battery pack does not pass the test, this LED will
flash prompting the user to change the battery pack.
I. Inverter LED:
This LED is lit when the inverter is supplying power to the load.
J. Inverter Static Switch LED:
This LED is lit when the inverter static switch is operating and
the reserve static switch is turned off. When this LED is on, the load is
supplied from the inverter. Usually this LED will stay lit for 7sec. after the
inverter is switched on.
K. Reserve Static Switch LED:
This LED is lit when the reserve static switch is operating and
the inverter static switch is turned off. When this LED is on, the load is being
supplied by the reserve. Since the reserve static switch and inverter static
switch will never operate simultaneously, the Inverter Static Switch LED and
the Reserve Static Switch LED will never be lit at the same time.
L. Output LED:
This LED is lit when there is AC power present at the output terminals.
M. Up key:
This is an LCD control key. It moves the cursor one field upward when items