M0703_NX_Series_Operators_Manual
V1.25
2012-06-12 27
6.6.3
FUSE RATING & CABLE SIZE FOR BATTERY BANKS
Table 6.6.3.1
Recommended Fuse and Cable Size for the Battery Banks
KVA Rating
Imax(A)
FUSE(A)
CABLE(mm²)
CABLE (AWG)
10 60 70 22 #6
15 60 70 22 #6
20 60 70 22 #6
30 90 100 38 #3
40 120 125 38 #2
50 150 175 50 0
60 180 200 80 00
80 240
125*2
38*2 #2
100 300 175*2
50*2 0
120 360 200*2
80*2 00
160 480 200*2
80*2 00
240 720 200*4
80*4 00
320 960 200*4
80*4 00
*THE BATTERY VOLTAGE IS 295 – 410V
**LEAD ACID BATTERY – 174 CELLS