Equivalent of pipe length in meters
Bend
Pipe diameter
Parallel
Air/fluegas
Ø150/Ø200 mm
Parallel
Air/fluegas
Ø150/Ø250 mm
Parallel
Air/fluegas
Ø180/Ø250 mm
Bend 90°
4.4
4.1
4.3
Bend 45°
2.2
1.9
2.1
Warning : Do not install the terminals for supply of combustion air and for the exhaust of combustion products on opposite walls of the building
Terminals should be installed in the same pressure area (within a plane of 1m2)
6.5.4
Pressure drop calculations
The first 90 ° bend must be mounted directly to the boiler and followed by the chimney silencer (this bend is not part of the calculation (as it is already
taken into account)).
Flue-outlet and air-supply calculations ;
Total pressure drop available for flue-outlet and air-supply is given in the table below.
Air connection :
All types have air connection Ø 150 mm
Flue gas connection :
Ø 250 mm for all types
Type Boiler
Total available Pressure drop
In [Pa] for B23, C33, C63
B 350
250
B 425
250
B 510
300
B 600
300
For pressure drop calculation of appliance types B23,C33 use the next two tables on the following pages.
Pressure drop table per component