- 8 -
StrikeIt1V
Note:
For independent operation of Output 1 and 2, connect NO
dry contact between IN1 and GND and/or IN2 and GND. For sequential operation of OUT1 and OUT2 install a jumper between IN1 and IN2 and a jumper between both GND terminals.
Battery
+ 24VDC
--
Output
1
24V Aux
+
Output
--
20VDC-26.
4VDC @ 0.75A
12V Aux
+
Output
--
12V
DC @ 0.75A in alarm,
0.5A in stand-by
OUT1 and OUT2
Relock delay adjustment. Used to hold OUT1 or OUT2 energized after a momentary closure across IN1 or IN2. Set for 0 seconds
for output to follow input. Turn clockwise to increase time.
AC Supervisio
n
Delayed 1 - This relay will
activate after 0.5 sec. or 1 sec.
FACP
GND
GND
– OUT1
+
+ BA
T
–
– OUT2
+
IN1
GND
IN2
LG
N
25A
32V
25A
6.3
A
6.3A
250V
AC
OUT1 TIME
R
Manual Te
st
OUT2 TIME
R
ON
Option 1 - Option 2
24-5V Hold Vo
ltage
Follow-up Delay 0.5-1 sec.
Fire Alarm Interface
1
2
3
4
Output
2
AC Power LE
D
MI
N
MAX
INP1
INP2
FAI
BAT
AC
Follower 1 - This relay will activate immediately when OUTPUT 1 is energized.
Delayed 2 - This relay wil
l
activate after 0.5 sec. or 1 sec.
Follower 2 - This relay will activate
immediately when OUTPUT 2 is energized.
C
NO
C
NO
C NC +12VDC–
+24VDC–
Delayed 1
Follower
1
C
NO
C
NO
C
NO
C
NO
Delayed 2
Follower
2
C
NO
C
NO
FA
ULT
C
NC
Fire Alarm Interface
Connect these terminals to a normally closed dry contact
that opens upon fire alarm activation.
Input #1
Connect normally open dry contacts from key switch, timer, remote release or any maintained/momentary
switch. Output #1 energizes while input is closed.
Input #2
Connect normally open dry contacts from key switch, timer, remote release or any maintained/momentary
switch. Output #2 energizes while input is closed.
Fig. 2