Altronix StrikeIt1V Скачать руководство пользователя страница 8

 

- 8 - 

StrikeIt1V

Note:

 For independent operation of Output 1 and 2, connect NO

dry contact between IN1 and GND and/or IN2 and GND. For sequential operation of OUT1 and OUT2 install a jumper between IN1 and IN2 and a jumper between both GND terminals.

Battery

 + 24VDC 

--

Output 

1

24V Aux 

Output

 --

20VDC-26.

4VDC @ 0.75A

12V Aux 

Output

 --

12V

DC @ 0.75A in alarm,

0.5A in stand-by

OUT1 and OUT2

Relock delay adjustment. Used to hold OUT1 or OUT2 energized after a momentary closure across IN1 or IN2. Set for 0 seconds

for output to follow input. Turn clockwise to increase time.

 

AC Supervisio

n

Delayed 1 - This relay will

activate after 0.5 sec. or 1 sec.

FACP

GND

GND

– OUT1 

+

+ BA

– OUT2 

+

IN1

GND

IN2

LG

N

25A

 32V

25A

6.3

A

6.3A

 250V

AC

OUT1 TIME

R

Manual Te

st

OUT2 TIME

R

ON

Option 1 - Option 2

24-5V Hold Vo

ltage

Follow-up Delay 0.5-1 sec.

Fire Alarm Interface

1

2

3

4

Output 

2

AC Power LE

D

MI

N

MAX

INP1

INP2

FAI

BAT

AC

Follower 1 - This relay will activate immediately when OUTPUT 1 is energized.

Delayed 2 - This relay wil

l

activate after 0.5 sec. or 1 sec.

Follower 2 - This relay will activate

immediately when OUTPUT 2 is energized.

 C 

NO 

NO

C      NC  +12VDC–

   +24VDC–

 Delayed 1 

Follower 

1

 C 

NO 

NO

 C 

NO 

NO

 Delayed 2 

Follower 

2

 C 

NO 

NO

 FA

ULT

 C 

NC

Fire Alarm Interface

Connect these terminals to a normally closed dry contact

that opens upon fire alarm activation.

Input #1

Connect normally open dry contacts from key switch, timer, remote release or any maintained/momentary

switch. Output #1 energizes while input is closed. 

Input #2

Connect normally open dry contacts from key switch, timer, remote release or any maintained/momentary

switch. Output #2 energizes while input is closed. 

Fig. 2

Содержание StrikeIt1V

Страница 1: ...Rev 052915 More than just power TM Panic Device Power Controller Installation Guide V...

Страница 2: ...on Instructions pg 4 StrikeIt1V LED Diagnostics pg 5 Maintenance pg 5 StrikeIt1V Terminal Identification pg 6 Compatible Panic Hardware Devices pg 6 Maximum Wiring Distance Table pg 6 NEC Power Limite...

Страница 3: ...requiring battery back up Auxiliary output rated 0 75A continuous supply current Not affected by FACP trigger One 1 12VDC filtered regulated auxiliary output rated 0 75A in alarm 0 5A stand by curren...

Страница 4: ...6 The panic hardware device operating voltage specifications must cover 20VDC to 26 4VDC range Note Refer to compatible panic hardware device list pg 6 5 Set lock output release time by adjusting OUT1...

Страница 5: ...iggered alarm condition Off FACP normal non alarm condition BAT Trouble Red Off Normal condition On Manual test initiated Slow Blink Battery low or missing active during manual test or AC failure AC T...

Страница 6: ...d Fig 3b pg 9 This permits the Panic Hardware Device to fully unlock before signaling auto operator to swing door Delayed 2 Dry form A contacts provide a 1 second momentary pulse after a preset delay...

Страница 7: ...2VDC 12VDC C NO C NO C NC 12VDC 24VDC FACP GND GND OUT1 BAT OUT2 IN1 GND IN2 L G N 25A 32V 25A 6 3A 6 3A 250V AC OUT1 TIMER Manual Test OUT2 TIMER ON Option 1 Option 2 24 5V Hold Voltage Follow up Del...

Страница 8: ...l Test OUT2 TIMER ON Option 1 Option 2 24 5V Hold Voltage Follow up Delay 0 5 1 sec Fire Alarm Interface 1 2 3 4 Output 2 AC Power LED MIN MAX INP1 INP2 FAI BAT AC Follower 1 This relay will activate...

Страница 9: ...Optional Rechargeable Stand by Battery Optional Rechargeable Stand by Battery FACP GND GND T1 OUT2 IN1 GND IN2 OUT1 TIMER Manual Test OUT2 TIMER ON Option 1 Option 2 24 5V Hold Voltage Follow up Delay...

Страница 10: ...different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge C...

Страница 11: ...StrikeIt1V 11 Notes...

Страница 12: ...rranty Made in U S A IIStrikeIt1V E30R MEMBER Enclosure Dimensions 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 6mm 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0...

Отзывы: