- 6 - 

StrikeIt1V

StrikeIt1V Terminal Identification:

Terminal Legend

Function/Description

L, G, N

Connect 220VAC, 50/60 Hz to these terminals: L to Hot, N to Neutral .

+ 12VDC –

12VDC Auxiliary Output @ 0 .75A in alarm, 0 .5A in stand-by .

+ 24VDC –

24VDC Auxiliary Output @ 0 .75A . 
20VDC to 26 .4VDC for applications with battery back-up .

+ BAT –

24VDC Stand-by Battery Connection (Two (2) 12VDC batteries wired in series) .

– OUT 1 +

Connect 24VDC Panic Hardware Device #1 (See compatibility chart for other UL Listed 
devices. Operating range of the device must cover 20VDC to 26.4VDC range 0.25 Ohm 
maximum wiring resistance)
 .

– OUT 2 + 

Connect 24VDC Panic Hardware Device #2 . (See compatibility chart for other UL 
Listed devices. Operating range of the device must cover 20VDC to 26.4VDC range 0.25 
Ohm maximum wiring resistance)
 .

FACP / GND

Normally Closed Dry Contact from Fire Alarm Control 
(100 Ohm maximum wiring resistance) .

IN1 / GND

Normally Open Trigger input controls Output 1 . May be held closed for extended unlocking 
(100 Ohm maximum wiring resistance)
 .

IN2 / GND

Normally Open Trigger input controls Output 2 . May be held closed for extended unlocking 
(100 Ohm maximum wiring resistance)
 .

Delayed 1

Dry form “A” contacts provide a 1 second momentary pulse after a preset delay . With DIP 
switch [SW3] in the OFF position, the delay is 0 .5 seconds . With DIP switch [SW3] in 
the ON position, the delay is 1 second (Fig. 3b, pg. 9) . This permits the Panic Hardware 
Device to fully unlock before signaling auto operator to swing door .

Delayed 2

Dry form “A” contacts provide a 1 second momentary pulse after a preset delay . With DIP 
switch [SW3] in the OFF position, the delay is 0 .5 seconds . With DIP switch [SW3] in 
the ON position, the delay is 1 second (Fig. 3b, pg. 9) . This permits the Panic Hardware 
Device to fully unlock before signaling auto operator to swing door .

Follower 1

Dry form “A” contact . Energizes while output 1 is energized . 
Enables outside ADA switch plate to actuate auto operator while door is unlocked . 
De-activates outside ADA actuator while door is locked .

Follower 2

Dry form “A” contact . Energizes while output 2 is energized . 
Enables outside ADA switch plate to actuate auto operator while door is unlocked . 
De-activates outside ADA actuator while door is locked .

Supervision

Indicates low DC output voltage condition . 
It may be caused by an AC brownout and low battery occuring simultaneously . 
Manual self test needs to be conducted to determine battery condition . 

Compatible Panic Hardware Devices:

Manufacturer

Model Number

First Choice

3600 - Concealed Vertical Rod Exit Device 
3700 - Rim Latching Exit Device

Kawneer

EL Paneline Exit Device

Von Duprin

®

EL98 Series Panic Hardware with Electric Latch Retraction

HES

7500 Electric Strike

Maximum Wiring Distance Table:

A maximum 0 .25 Ohm resistance of connecting wires is acceptable, see chart below for wire gauge and distances .

Wire Gauge

Distance

14 AWG Stranded

40 ft .

12 AWG Stranded

60 ft .

10 AWG Stranded

100 ft .

Содержание StrikeIt1V

Страница 1: ...Rev 052915 More than just power TM Panic Device Power Controller Installation Guide V...

Страница 2: ...on Instructions pg 4 StrikeIt1V LED Diagnostics pg 5 Maintenance pg 5 StrikeIt1V Terminal Identification pg 6 Compatible Panic Hardware Devices pg 6 Maximum Wiring Distance Table pg 6 NEC Power Limite...

Страница 3: ...requiring battery back up Auxiliary output rated 0 75A continuous supply current Not affected by FACP trigger One 1 12VDC filtered regulated auxiliary output rated 0 75A in alarm 0 5A stand by curren...

Страница 4: ...6 The panic hardware device operating voltage specifications must cover 20VDC to 26 4VDC range Note Refer to compatible panic hardware device list pg 6 5 Set lock output release time by adjusting OUT1...

Страница 5: ...iggered alarm condition Off FACP normal non alarm condition BAT Trouble Red Off Normal condition On Manual test initiated Slow Blink Battery low or missing active during manual test or AC failure AC T...

Страница 6: ...d Fig 3b pg 9 This permits the Panic Hardware Device to fully unlock before signaling auto operator to swing door Delayed 2 Dry form A contacts provide a 1 second momentary pulse after a preset delay...

Страница 7: ...2VDC 12VDC C NO C NO C NC 12VDC 24VDC FACP GND GND OUT1 BAT OUT2 IN1 GND IN2 L G N 25A 32V 25A 6 3A 6 3A 250V AC OUT1 TIMER Manual Test OUT2 TIMER ON Option 1 Option 2 24 5V Hold Voltage Follow up Del...

Страница 8: ...l Test OUT2 TIMER ON Option 1 Option 2 24 5V Hold Voltage Follow up Delay 0 5 1 sec Fire Alarm Interface 1 2 3 4 Output 2 AC Power LED MIN MAX INP1 INP2 FAI BAT AC Follower 1 This relay will activate...

Страница 9: ...Optional Rechargeable Stand by Battery Optional Rechargeable Stand by Battery FACP GND GND T1 OUT2 IN1 GND IN2 OUT1 TIMER Manual Test OUT2 TIMER ON Option 1 Option 2 24 5V Hold Voltage Follow up Delay...

Страница 10: ...different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge C...

Страница 11: ...StrikeIt1V 11 Notes...

Страница 12: ...rranty Made in U S A IIStrikeIt1V E30R MEMBER Enclosure Dimensions 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 6mm 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0...

Отзывы: