Altronix StrikeIt1V Скачать руководство пользователя страница 5

 

StrikeIt1V 

- 5 -

10 .  When using stand-by batteries, they must be lead acid or gel type . 7AH batteries will provide 30 minutes of 
 

backup time . Connect two (2) 12VDC batteries wired in series to the terminals marked [+ BAT –] . 

 

For Access Control applications batteries are optional, for Canadian applications batteries are required . 

 

When batteries are not used, loss of AC will result in the loss of output voltage .

11 .  Mount UL Listed tamper switch (Sentrol model 3012 or equivalent) at the top of the enclosure . Slide the 
 

tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Fig. 3, pg. 9) . 

 

Connect tamper switch wiring to the Access Control Panel input or the appropriate 

 

UL Listed reporting device . To activate alarm signal open the door of the enclosure .

 

Note: Do not exceed voltage and current ratings of tamper switch . 

 

Please refer to tamper switch installation instructions .

12 .  Upon completion of wiring secure enclosure door with screws or cam lock (supplied) .

StrikeIt1V LED Diagnostics:

LED

LED Status

Panic Device Power Controller Status

Power -
Green (AC)

On

Normal operating condition .

Off

Loss of AC .

INP1 - Red
Trigger Input 1

On

Output 1 - Energized .

Slow Blink

Output 1 - Open Circuit .

Rapid Blink

Output 1 - Short Circuit .

Off

Output 1 - De-energized .

INP2 - Red
Trigger Input 2

On

Output 2 - Energized .

Slow Blink

Output 2 - Open Circuit .

Rapid Blink

Output 2 - Short Circuit .

Off

Output 2 - De-energized .

FAI - Green

On

FACP Input triggered (alarm condition) .

Off

FACP normal (non-alarm condition) .

BAT Trouble
Red

Off

Normal condition .

On

Manual test initiated .

Slow Blink

Battery low or missing, active during manual test or AC failure .

AC Trouble
Green

Off

AC normal .

Slow blink

AC low or missing .

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:
FACP Supervision: 

To ensure proper connection and operation of the Fire Alarm disconnect hookup, 

 

remove wire from the terminal marked [FACP] on StrikeIt1V . With the DIP switch 

 

[SW4] in ON positon, unlocked Panic Hardware Devices will unlock . With DIP switch 

 

[SW4] in the OFF position (Fig. 3b, pg. 9), locked Panic Hardware Devices will relock .

Output Voltage Test:  Under normal load conditions the DC output voltage should be checked for proper 
 

voltage level .

Battery Test: 

Under normal load conditions check that the battery is fully charged, check specified 

 

voltage both at battery terminal and at the board terminals marked [+ BAT –] to ensure 

 

that there is no break in the battery connection wires . Press Manual test button . 

 

The battery LED should be illuminated during the self-test (approximately 15 seconds . 

 

When the battery LED blinks slowly, this indicates that the battery is low or missing and 

 

may need to be replaced or serviced .

 Note: Maximum charging current under discharge is 650mA .
 Note: Expected battery life is 5 years; however it is recommended changing batteries in 
 

4 years or less if needed .

Caution: 

For continuous protection against risk of electric shock and fire hazard, replace input 

 

fuse with the same type and rating: 6 .3A/250V . 

 

Do not expose to rain or moisture; indoor use only .

Содержание StrikeIt1V

Страница 1: ...Rev 052915 More than just power TM Panic Device Power Controller Installation Guide V...

Страница 2: ...on Instructions pg 4 StrikeIt1V LED Diagnostics pg 5 Maintenance pg 5 StrikeIt1V Terminal Identification pg 6 Compatible Panic Hardware Devices pg 6 Maximum Wiring Distance Table pg 6 NEC Power Limite...

Страница 3: ...requiring battery back up Auxiliary output rated 0 75A continuous supply current Not affected by FACP trigger One 1 12VDC filtered regulated auxiliary output rated 0 75A in alarm 0 5A stand by curren...

Страница 4: ...6 The panic hardware device operating voltage specifications must cover 20VDC to 26 4VDC range Note Refer to compatible panic hardware device list pg 6 5 Set lock output release time by adjusting OUT1...

Страница 5: ...iggered alarm condition Off FACP normal non alarm condition BAT Trouble Red Off Normal condition On Manual test initiated Slow Blink Battery low or missing active during manual test or AC failure AC T...

Страница 6: ...d Fig 3b pg 9 This permits the Panic Hardware Device to fully unlock before signaling auto operator to swing door Delayed 2 Dry form A contacts provide a 1 second momentary pulse after a preset delay...

Страница 7: ...2VDC 12VDC C NO C NO C NC 12VDC 24VDC FACP GND GND OUT1 BAT OUT2 IN1 GND IN2 L G N 25A 32V 25A 6 3A 6 3A 250V AC OUT1 TIMER Manual Test OUT2 TIMER ON Option 1 Option 2 24 5V Hold Voltage Follow up Del...

Страница 8: ...l Test OUT2 TIMER ON Option 1 Option 2 24 5V Hold Voltage Follow up Delay 0 5 1 sec Fire Alarm Interface 1 2 3 4 Output 2 AC Power LED MIN MAX INP1 INP2 FAI BAT AC Follower 1 This relay will activate...

Страница 9: ...Optional Rechargeable Stand by Battery Optional Rechargeable Stand by Battery FACP GND GND T1 OUT2 IN1 GND IN2 OUT1 TIMER Manual Test OUT2 TIMER ON Option 1 Option 2 24 5V Hold Voltage Follow up Delay...

Страница 10: ...different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge C...

Страница 11: ...StrikeIt1V 11 Notes...

Страница 12: ...rranty Made in U S A IIStrikeIt1V E30R MEMBER Enclosure Dimensions 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 6mm 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0...