- 10 - StrikeIt1V
NEC Power-Limited Wiring Requirements for StrikeIt1V Model:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet . All power-limited
circuit wiring must remain at least 0 .25” away from any non power-limited circuit wiring . Furthermore, all
power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through differ-
ent conduits . One such example of this is shown below . Your specific application may require different conduit
knockouts to be used . Any conduit knockouts may be used . For power- limited applications, use of conduit is
optional . All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or
equivalent substitute) .
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 4a).
Fig. 4
Fig. 4a
Delayed/Follower
Connections
Input
220VAC,
50/60Hz
Battery
Connections
Locking Device
Connections
FACP and
Access Control
Trigger Inputs
Aux . Outputs
AC Supervision
External
Jacketed
Shield
Incorrect Wire
Handling
Correct Wire
Handling
Pull back
external jacketed
shield approx. 1/2”.
Wire
Insulation
Solid Copper
Conductors