- 10 - StrikeIt1V

NEC Power-Limited Wiring Requirements for StrikeIt1V Model:

Power-limited and non power-limited circuit wiring must remain separated in the cabinet . All power-limited 
circuit wiring must remain at least 0 .25” away from any non power-limited circuit wiring . Furthermore, all 
power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through differ-
ent conduits . One such example of this is shown below . Your specific application may require different conduit 
knockouts to be used . Any conduit knockouts may be used . For power- limited applications, use of conduit is 
optional . All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or 
equivalent substitute) .
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 4a).

Fig. 4

Fig. 4a

Delayed/Follower

Connections

Input

220VAC, 

50/60Hz

Battery

Connections

Locking Device 

Connections

FACP and

Access Control

Trigger Inputs

Aux . Outputs

AC Supervision

External

Jacketed

Shield

Incorrect Wire

Handling

Correct Wire

Handling

Pull back

external jacketed

shield approx. 1/2”.

Wire

Insulation

Solid Copper

Conductors

Содержание StrikeIt1V

Страница 1: ...Rev 052915 More than just power TM Panic Device Power Controller Installation Guide V...

Страница 2: ...on Instructions pg 4 StrikeIt1V LED Diagnostics pg 5 Maintenance pg 5 StrikeIt1V Terminal Identification pg 6 Compatible Panic Hardware Devices pg 6 Maximum Wiring Distance Table pg 6 NEC Power Limite...

Страница 3: ...requiring battery back up Auxiliary output rated 0 75A continuous supply current Not affected by FACP trigger One 1 12VDC filtered regulated auxiliary output rated 0 75A in alarm 0 5A stand by curren...

Страница 4: ...6 The panic hardware device operating voltage specifications must cover 20VDC to 26 4VDC range Note Refer to compatible panic hardware device list pg 6 5 Set lock output release time by adjusting OUT1...

Страница 5: ...iggered alarm condition Off FACP normal non alarm condition BAT Trouble Red Off Normal condition On Manual test initiated Slow Blink Battery low or missing active during manual test or AC failure AC T...

Страница 6: ...d Fig 3b pg 9 This permits the Panic Hardware Device to fully unlock before signaling auto operator to swing door Delayed 2 Dry form A contacts provide a 1 second momentary pulse after a preset delay...

Страница 7: ...2VDC 12VDC C NO C NO C NC 12VDC 24VDC FACP GND GND OUT1 BAT OUT2 IN1 GND IN2 L G N 25A 32V 25A 6 3A 6 3A 250V AC OUT1 TIMER Manual Test OUT2 TIMER ON Option 1 Option 2 24 5V Hold Voltage Follow up Del...

Страница 8: ...l Test OUT2 TIMER ON Option 1 Option 2 24 5V Hold Voltage Follow up Delay 0 5 1 sec Fire Alarm Interface 1 2 3 4 Output 2 AC Power LED MIN MAX INP1 INP2 FAI BAT AC Follower 1 This relay will activate...

Страница 9: ...Optional Rechargeable Stand by Battery Optional Rechargeable Stand by Battery FACP GND GND T1 OUT2 IN1 GND IN2 OUT1 TIMER Manual Test OUT2 TIMER ON Option 1 Option 2 24 5V Hold Voltage Follow up Delay...

Страница 10: ...different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge C...

Страница 11: ...StrikeIt1V 11 Notes...

Страница 12: ...rranty Made in U S A IIStrikeIt1V E30R MEMBER Enclosure Dimensions 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 6mm 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0...

Отзывы: