Overview:
Altronix StrikeIt1V will operate up to two (2) 24VDC panic hardware devices simultaneously . It is designed to
handle the high current surge panic hardware locking devices demand . Each lock output has an adjustable relock
delay timer . It will control a pair of doors simultaneously or independently control two individual doors . It has a
follower relay for each output to trigger external relays, ADA push plate switches, etc . Delayed follower relays
control automatic door operators for doors that are always locked or for doors that are unlocked during the business
day . In addition, two un-switched auxiliary voltage outputs are provided for powering card readers, keypads, REX
PIRs, electronic timers, relays, etc . A configurable FACP interface will either provide power or remove power to
the lock outputs when activated . LED status indicators are provided to monitor AC power, FACP status and for
lock output wiring supervision . Intelligent logic provides protection against accidental shorting of lock outputs .
Specifications:
Input:
• Input 220VAC, 50/60Hz, 4A .
• Two (2) NO trigger inputs .
• Input fuse rating: 6 .3A .
Outputs:
• Power options:
- Two (2) 20VDC to 26 .4VDC individually
controlled lock outputs for applications with
battery
back-up .
24VDC for applications without battery back-up
(US applications only) .
Current rating 15A for 300ms, 0 .75A continuous
supply
current .
- 5V holding voltage with 20VDC to 26 .4VDC
initial 100ms pulse .
Maximum total 5V holding current of both
outputs is 0 .74A .
• One (1) 20VDC to 26 .4VDC for applications with
battery back-up, 24VDC for applications in US not
requiring battery back-up .
Auxiliary output rated @ 0 .75A continuous supply
current (Not affected by FACP trigger) .
• One (1) 12VDC filtered regulated auxiliary output
rated @ 0 .75A in alarm, 0 .5A stand-by current
(Not affected by FACP trigger) .
• Two (2) follower form “A” SPST relay outputs
rated @ 0 .6A/28VDC .
Relays energize while input is closed .
• Two (2) delayed follower Normally Open relay
outputs rated @ 0 .6A/28VDC .
Delay time is selectable 0 .5 seconds or 1 second .
Energized duration is 1 second .
• Trouble relay output indicating low DC
output voltage .
Battery Backup:
• Battery leads included .
• Battery fuse rating: 25A/32V .
• Maximum charge current 650mA .
• Built-in charger for sealed lead acid or
gel type batteries .
• Automatic switch over to stand-by battery
when AC fails .
• When 7AH batteries are used, battery capacity
for emergency stand-by is 30 minutes .
Visual Indicators:
• Green AC Power LED indicates 220VAC present .
• Red trigger input LEDs indicate panic device
status/trouble (activated, short or open circuit) .
• Green Fire Alarm Interface (FAI) LED indicates
FACP disconnect is activated .
• Red Battery LED indicates low battery during
AC failure and manual test .
• Green AC LED indicates loss of AC trouble
(not active during manual test sequence) .
Fire Alarm Disconnect:
• Normally Closed FACP trigger input .
• Programmable Fire Alarm Disconnect options:
- Removes power to outputs and disables delayed
follower
relays .
- Connects power to lock outputs and enables
delayed follower relays .
Additional Features:
• Manual testing to allow to tests battery conditions .
• Adjustable panic release from 1 sec . to 30 secs .
Note: Follower and Delay relay turns off when the
potentiometer selected time elapses after release of
the input trigger .
• Cam lock included .
Enclosure Dimensions
(H x W x D approx.)
:
13 .5” x 13” x 3 .25” (342 .9mm x 330 .2mm x 82 .6mm)