background image

 

- 6 - 

Maximal3FDV/5FDV/7FDV Series (PTC) Installation Guide

15. 

Multiple power supply inputs

 (Fig. 2, pg. 8)

:

 

When using an additional external power supply, jumpers J1 and J2 located on corresponding ACM8 

 

board must be cut 

(Fig. 2c, 2d, pg. 8)

. Connect external access control power supply to the terminals 

 

marked [– C] (These terminals are paralleled to the [– Power +] terminals). When using DC power 

 

supplies, polarity must be observed. When using AC power supplies, polarity needs not to be observed. 

 

(Fig. 2d, pg. 8) 

All field wiring connections must be made employing suitable gauge CM or FPL jacketed 

 

wire or equivalent substitute 

(Fig. 4a, pg. 10).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

  FACP Supervision: 

To ensure proper connection and operation of the Fire Alarm disconnect 

     

 

hookup, please follow the appropriate procedure below:

 

Normally Open Input:

 Placing a short between terminals marked [T] and [+ INP] will trigger the 

     

 

Fire Alarm Disconnect. Remove the short to reset.

 

Normally Closed Input:

 

Removing the wire from terminal marked [INP –] will trigger the Fire Alarm 

     

 

Disconnect. Replace the wire to terminal marked [INP –] to reset.

 

FACP Signal Circuit Input:

  It is necessary to trigger the Fire Alarm System. In all of the above scenarios 

     

 

the green TRG LED of the ACM8s will illuminate. All outputs selected for 

     

 

Fire Alarm Disconnect will activate releasing locking devices.

 

Note:

 All outputs [OUT 1 - OUT 8] must be in a normal (de-energized) condition prior to testing. When the 

  unit is configuredfor Normally Open 

(Fig. 7, pg. 11)

 or Normally Closed 

(Fig. 9, pg. 11)

 latching operation 

  it is necessary to reset the Fire Alarm Disconnect by activating the Normally Closed reset switch.

Output Voltage Test:

 

Under normal load conditions, the DC output voltage should be checked for 

     

 

proper voltage level (refer to 

MaximalFDV series Configuration Chart, pg. 3

).

Battery Test:

 

Under normal load conditions check that the battery is fully charged, check 

     

 

specified voltage at the battery terminals and at the board terminals marked 

     

[+ 

BAT 

–] to ensure that there is no break in the battery connection wires.

Note:

 Maximum charge current is 1.54A. Expected battery life is 5 years; however, it is recommended to 

change batteries within 4 years or less if necessary.

Power Supply Board LED Diagnostics:

Red (DC)

Green (AC/AC1)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Red (Bat)

Battery Status

ON

Normal operating condition.

OFF

Battery fail/low battery.

Access Power Controller LED Diagnostics:

LED

ON

OFF

LED 1- LED 8 (Red)

Output relay(s) energized.

Output relay(s) de-energized.

Trg (Green)

FACP input triggered (alarm condition).

FACP normal (non-alarm condition).

Содержание Maximal 3FDV

Страница 1: ...utputs Maximal5FDV 12VDC 8 6A Sixteen 16 PTC protected outputs Maximal7FDV 24VDC 9 2A Sixteen 16 PTC protected outputs Rev SFDV031115 More than just power TM Installing Company ________________ Servic...

Страница 2: ...LED Diagnostics pg 6 Access Power Controller LED Diagnostics pg 6 Power Supply Board Terminal Identification pg 6 Access Power Controller Terminal Identification pg 7 Power Supply Board Stand by Batt...

Страница 3: ...0 19 26 4 12VDC 4 6A or 24VDC 5 2A 16 2 1A 2 5 5A 250V 10A 32V 10A 250V Maximal5FDV 9 7 13 2 10 03 13 2 8 6A 16 2 1A 2 5 5A 250V 15A 32V 10A 250V Maximal7FDV 19 8 26 4 20 28 26 4 9 2A 16 2 7A 2 5 6 3A...

Страница 4: ...Terminal Identification pg 7 Power Supply Board Stand by Battery Specifications pg 7 Power Supply Board Output Voltage Settings pg 7 Access Power Controller Typical Application Diagram pg 8 FACP Optio...

Страница 5: ...For latching hook up refer to Fig 9 pg 11 c FACP Signaling Circuit input trigger Connect the positive and negative from the FACP signaling circuit output to the terminals marked INP Connect the FACP E...

Страница 6: ...ill illuminate All outputs selected for Fire Alarm Disconnect will activate releasing locking devices Note All outputs OUT 1 OUT 8 must be in a normal de energized condition prior to testing When the...

Страница 7: ...er factory connected These terminals are paralleled to the Control terminals Control These terminals are paralleled to the Power terminals These terminals can be connected to an external access contro...

Страница 8: ...ND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LED4 LED5 LED6 LED7 LED8 J2 FACP NC C NO COM OUTPUT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET NC C NO C...

Страница 9: ...8 INPUT TRIGGER 10A 250V INP T RET NO C NC FACP INTERFACE Power Control F1 F2 F3 F4 F5 F6 F7 F8 MAIN TRG FACP 1 2 3 4 1 2 3 4 O N O N 1 2 3 4 1 2 3 4 O N O N Optional Rechargeable Stand by Battery BAT...

Страница 10: ...ctions must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring metho...

Страница 11: ...O C NC FACP INTERFACE JUMPER N C DRY TRIGGER INPUT TRG NO C NC FACP INTERFACE FACP N C TRIGGER INPUT N C RESET SWITCH JUMPER TRG FACP N O TRIGGER INPUT TRG FACP NO C NC FACP INTERFACE N C RESET SWITCH...

Страница 12: ...4mm 8 9 226 1mm 8 4 213 4mm 19 482 6mm 4 101 6mm 1 25 4mm 7 5 190 5mm 5 127mm 26 660 4mm 1 5 38 1mm 1 0 25 4mm 6 25 158 8mm 8 5 215 9mm 7 5 190 5mm 10 254mm 26 660 4mm 1 25 31 8mm 7 177 8mm 7 177 8mm...

Отзывы: