Maximal3FDV/5FDV/7FDV Series (PTC) Installation Guide 

- 7 -

Power Supply Board Terminal Identification:

Terminal Legend

Function/Description

L, N

Connect 220VAC 50/60Hz to these terminals: L to hot, N to neutral. 

Do not use terminal marked [G]

+ DC – 

Factory connected to ACM8 board.

Trigger EOL

Supervised

Fire Alarm Interface trigger input from a short or FACP. Trigger inputs can be normally 

open, normally closed from an FACP output circuit 

(Fig. 3, pg. 9)

.

NO, GND RESET

FACP interface latching or non-latching 

(Fig. 3, pg. 9)

.

+ AUX – 

Auxiliary output rated @ 1A (unswitched) 

(Fig. 3, pg. 9)

.

AC FAIL

NC, C, NO

Indicates loss of AC power, e.g. connect to audible device or alarm panel. 

Relay normally energized when AC power is present. 

Contact rating 1A @ 30VDC 

(Fig. 3, pg. 9)

.

BAT FAIL

NC, C, NO

Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized 

when DC power is present. Contact rating 1A @ 30VDC. 

A removed battery is reported within 5 minutes. 

Battery reconnection is reported within 1 minute 

(Fig. 3, pg. 9)

.

+ BAT –

Stand-by battery connections. 

Maximum charge current 1.54A 

(Fig. 3, pg. 9)

.

 

Access Power Controller Terminal Identification:

Terminal Legend

Function/Description

– Power +

12VDC or 24VDC from power supply/charger (factory connected).

These terminals are paralleled to the [– C] terminals.

– C

These terminals are paralleled to the [– Power +] terminals.

These terminals can be connected to an external access control power supply to provide 

isolated operating power for the devices. Jumpers J1 and J2 must be removed.

TRIGGER INPUT1 - 

INPUT 8 IN, GND

From normally open and/or open collector sink trigger inputs 

(request to exit buttons, exit PIRs, etc.)

OUTPUT 1-

OUTPUT 8 

NC, C, NO, COM

12VDC to 24VDC trigger controlled outputs are rated at 2.5A.

Maximal3FDV

 - 10.0-13.2VDC @ 4.6A or 20.19-26.4VDC @ 5.2A.

Maximal5FDV

 - 10.03-13.2VDC @ 8.6A.

Maximal7FDV

 - 20.17-26.4VDC @ 9.2A.

Fail-Safe [NC positive (+) & COM Negative (–)], Fail-Secure [NO positive (+) & 

COM Negative (–)], Auxiliary output [C positive (+) & COM Negative (–)]. 

When using AC power supplies polarity needs not to be observed. 

Contacts shown in a non-triggered state.

FACP INTERFACE

T, + INPUT –

Fire Alarm Interface trigger input from FACP. Trigger inputs can be normally open,

normally closed from an FACP signaling circuit output 

(Figs. 5-9, pg. 11).

FACP INTERFACE

NC, C, NO

Form “C” relay contact rated @ 1A 28VDC for alarm reporting.

Power Supply Board Stand-by Battery Specifications:

Battery

Maximal3FDV

Maximal5FDV

Maximal7FDV

7AH

10 Mins./6A

5 Mins./10A

5 Mins./10A

12AH

30 Mins./6A

30 Mins./10A

30 Mins./10A

40AH

Over 4 Hours/6A

Over 2 Hours/10A

Over 2 Hours/10A

65AH

Over 4 Hours/6A

Over 4 Hours/10A

Over 4 Hours/10A

Содержание Maximal 3FDV

Страница 1: ...utputs Maximal5FDV 12VDC 8 6A Sixteen 16 PTC protected outputs Maximal7FDV 24VDC 9 2A Sixteen 16 PTC protected outputs Rev SFDV031115 More than just power TM Installing Company ________________ Servic...

Страница 2: ...LED Diagnostics pg 6 Access Power Controller LED Diagnostics pg 6 Power Supply Board Terminal Identification pg 6 Access Power Controller Terminal Identification pg 7 Power Supply Board Stand by Batt...

Страница 3: ...0 19 26 4 12VDC 4 6A or 24VDC 5 2A 16 2 1A 2 5 5A 250V 10A 32V 10A 250V Maximal5FDV 9 7 13 2 10 03 13 2 8 6A 16 2 1A 2 5 5A 250V 15A 32V 10A 250V Maximal7FDV 19 8 26 4 20 28 26 4 9 2A 16 2 7A 2 5 6 3A...

Страница 4: ...Terminal Identification pg 7 Power Supply Board Stand by Battery Specifications pg 7 Power Supply Board Output Voltage Settings pg 7 Access Power Controller Typical Application Diagram pg 8 FACP Optio...

Страница 5: ...For latching hook up refer to Fig 9 pg 11 c FACP Signaling Circuit input trigger Connect the positive and negative from the FACP signaling circuit output to the terminals marked INP Connect the FACP E...

Страница 6: ...ill illuminate All outputs selected for Fire Alarm Disconnect will activate releasing locking devices Note All outputs OUT 1 OUT 8 must be in a normal de energized condition prior to testing When the...

Страница 7: ...er factory connected These terminals are paralleled to the Control terminals Control These terminals are paralleled to the Power terminals These terminals can be connected to an external access contro...

Страница 8: ...ND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LED4 LED5 LED6 LED7 LED8 J2 FACP NC C NO COM OUTPUT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET NC C NO C...

Страница 9: ...8 INPUT TRIGGER 10A 250V INP T RET NO C NC FACP INTERFACE Power Control F1 F2 F3 F4 F5 F6 F7 F8 MAIN TRG FACP 1 2 3 4 1 2 3 4 O N O N 1 2 3 4 1 2 3 4 O N O N Optional Rechargeable Stand by Battery BAT...

Страница 10: ...ctions must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring metho...

Страница 11: ...O C NC FACP INTERFACE JUMPER N C DRY TRIGGER INPUT TRG NO C NC FACP INTERFACE FACP N C TRIGGER INPUT N C RESET SWITCH JUMPER TRG FACP N O TRIGGER INPUT TRG FACP NO C NC FACP INTERFACE N C RESET SWITCH...

Страница 12: ...4mm 8 9 226 1mm 8 4 213 4mm 19 482 6mm 4 101 6mm 1 25 4mm 7 5 190 5mm 5 127mm 26 660 4mm 1 5 38 1mm 1 0 25 4mm 6 25 158 8mm 8 5 215 9mm 7 5 190 5mm 10 254mm 26 660 4mm 1 25 31 8mm 7 177 8mm 7 177 8mm...

Отзывы: